4.

Wiring techniques

Wiring techniques
ENG
The wiring of FX
2N
associated products concern is felt, please contact a professional electrician who is trained to the local and national
standards applicable to the installation site.
Raccordement électrique
FRE
Les appareils FX
2N
incertitudes persistent, n'hésitez pas à consulter un électricien compétent qualifié et formé à l'utilisation des normes
électrotechniques locales et nationales.
Elektrischer Anschluss
GER
Die FX
- Geräte wurden so konstruiert, dass eine einfache und sichere Verdrahtung gewährleistet ist. Wenn während der
2N
Installation etwas unklar ist, sollten Sie auf jeden Fall eine Elektrofachkraft zu Rate ziehen, die für die Anwendung der
lokalen und nationalen elektrotechnischen Bestimmungen qualifiziert und ausgebildet ist.

Allacciamento elettrico

ITL
Gli apparecchi FX
2N
qualcosa non fosse chiaro, si raccomanda di consultare in ogni caso uno specialista elettrico, qualificato e istruito per
l'applicazione delle normative elettrotecniche locali e nazionali.
Conexión eléctrica
ESP
Las unidades FX
2N
problemas durante la instalación, se deberá recurrir a la ayuda de un electricista capacitado, que disponga de la
formación correspondiente que le permita observar y considerar las disposiciones electrotécni-cas locales y nacionales.
4.1

Wiring cautions

Wiring cautions
ENG
Do not run input signals in the same multicore cable as output signals or allow them to share the same wire.
Do not lay I/O signal cables next to power cables or allow them to share the same trunking duct. Low voltage
cables should be reliably separated or insulated with regard to high voltage cabling.
Where I/O signal lines are used over an extended distance consideration for voltage drop and noise interference
should be made.
Do not lay signal cables near high voltage power cabling or cabinet housing along the same trunking duct. Effects
of noise or surge induction may occur. Keep signal cables of more than 100 mm (3.94") away from these power
cables.
Cut off all phases from the power source before installation or performing wiring work to avoid electric shock.
Incorrect operation can lead to serious damage to the product.
Cut off all phases from the power source before installing/removing extension or communication cables to modules
to avoid electric shock, incorrect operation or serious damage to the product.
Replace the terminal cover provided, after installation or wiring work is completed, and before supplying power and
operating the unit to avoid electric shock.
After reading the manual's safety instruction, initiate the operation for making program changes while the PLC is in
RUN mode, forcing ON/OFF, and switching RUN/STOP.
The power supply of the extension units/blocks and the special function units/blocks should be started at the same
time or earlier than the FX
DO NOT use the """ terminal in PLC.
When performing incorrect wiring or operation, serious damage will occur.
products has been designed to be safe and easy. If during the installation of these product or
ont été conçus de manière à assurer un câblage simple et sûr. Si lors de leur installation des
sono stati costruiti in modo da garantire un cablaggio semplice e sicuro. Se durante l'installazione
han sido diseñadas, de manera que quede garantizado un cableado simple y seguro. En caso de
Series main unit.
2N
Wiring techniques 4
4.
4.
4.
4.
4.
4.1
4-1
1
2
3
4
5
6
7
A
B