11. Troubleshooting (Cont'd.)
Figure 7
Controller Status
Low/No Input Voltage
Controller is in Program Mode
Flashes
Controller Status
Constant
Standby/Low Voltage
Blinking
Pump Running
Number
Controller Status
of
Flashes
Controller Action
Constant
Controller Error
To clear the fault,
turn off power to the
controller, wait 1 minute,
turn on power to the
controller. If fault persists
contact installer.
No Light
Description
Check the input voltage to the controller. Measure the voltage between
L1 and L2 using an AC Voltmeter. This voltage should be greater than
190Vac.
Check the position of the "RUN/PRG Jumper". The "RUN/PRG Jumper" is
located in the upper lefthand corner of the controller. Refer to Figure 4.
Placing this jumper in "PRG" mode (Program Mode) allows the user to
update the controller's software through the "Comm. Port"
(Communications Port). Consult the factory for details on updating the
controller's software. When this jumper is in "RUN" mode (Run Mode),
the controller will operate normally.
If the controller is powered while in Program Mode, the status indicator
will not turn on. To return the controller to Run Mode turn the power off
to the controller and wait 5 minutes. Then move the "RUN/PRG Jumper"
to "RUN". Apply power to the controller. The controller is now in
Run Mode.
Green Light Codes
Description
Constant Green Light indicates the pump is off. The system is in Standby
mode when there is no fl ow in the system and the pressure setting has
been reached. The system is in a Low Voltage condition when the line
input voltage drops below 190VAC.
Flashing Green Light indicates the pump is running.
Red Light Codes
Fault Description.
This information is to be used by professional installers or qualifi ed
personnel only.
Internal controller fault. Replace controller.
15