安全信息
额定值数据
常规技术数据
7.
电源
电源电压(L1, L2, L3)
D2-4-xxx ......................................................................................... 3 x 200Vac to 440Vac (+10%/-15%)
D2-5-xxx ......................................................................................... 3 x 200Vac to 575Vac (+10%/-15%)
电源频率(起动时) .................................................................................................................. 45Hz 到 66Hz
额定绝缘电压 ...................................................................................................................................... 600Vac
指定型式 ............................................................................................................ 旁路半导体电机起动器型式 1
控制电源
控制电压(CSL, CSR, CSH) ............................................................................... 110-240Vac (+ 10% / - 15%)
............................................................................................................. 或者 380-440Vac (+ 10% / - 15%)
电流消耗(运转时) ................................................................... < 100mA
电流消耗(起动时) ................................................................................................................................. 10A
输入
起动(端子 DI1) ........................................................ 常开,150 k @ 300 Vac
停止(端子 DI2) .................................................................................................... 常闭,150 k @ 300 Vac
输出
主接触器(端子 COM2, RLO2) ............................................................. 常开
.................................................................................................... 6A, 30Vdc 电阻性 / 2A, 400Vac, AC11
可编程继电器(端子 COM1, RLO1) ......................................................... 常开
.................................................................................................... 6A, 30Vdc 电阻性 / 2A, 400Vac, AC11
环境
保护等级 CS018 到 CS085 .................................................................................................................... IP20
保护等级 CS140 到 CS200 .................................................................................................................... IP00
工作温度 ................................................................................................................................. -10°C 到+60°C
贮存温度 ...................................................................................... -25°C 到+60°C (24 小时以内可达 70°C)
湿度 .................................................................................................................................... 5%-95%相对湿度
污染等级 ....................................................................................................................................... 污染等级 3
振动 IEC 60068 测试 Fc 正弦波
.................................................................................................................... 4Hz 到 13.2Hz:±1mm 位移
......................................................................................................................... 13.2Hz 到 200Hz:±0.7g
EMC 辐射
设备类别(EMC) ..................................................................................................................................... A 类
传导射频辐射 ............................................................................................ 0.15MHz 到 0.5MHz:<90dB (µV)
................................................................................................................ 0.5MHz 到 5MHz:<76dB (µV)
.............................................................................................................. 5MHz 到 30MHz:80-60dB (µV)
辐射射频辐射: ................................................ 30MHz 到 230MHz:<30dB (µV/m)
..................................................................................................... 230MHz 到 1000MHz:<37dB (µV/m)
EMC 抗扰度
静电放电 ......................................................................................................... 4 kV 接触放电,8 kV 空气放电
射频电磁场 ............................................................................................ 0.15MHz 到 1000MHz:140dB (µV)
额定脉冲耐压(快速瞬态 5/50ns) ................................................................. 2kV 线路对地, 1kV 线路对线路
压降和短时间断电 ............................................................................................ 100 ms(额定电压的 40%)
谐波和失真 ................................................................................... IEC61000-2-4(3 类),EN/IEC61800-3
短路
额定短路电流 CS018 到 CS085 ............................................................................................................. 5 kA
额定短路电流 CS085 到 CS200 ........................................................................................................... 10 kA
120
机械安装
电气安装
www.controltechniques.com
可编程参数
诊断
常规技术数据
任选件
1
Digistart CS 用户指南
第二版