Diagnostics
6.1
LEDs
Figure 6-1 Feedback LEDs
6.2
Trip codes
The Ready LED will flash a different number of times to indicate the cause of the trip.
Table 6-1 Trip messages
Ready LED
Power Circuit: Check mains supply (L1, L2, L3), motor circuit (T1, T2, T3), soft starter SCRs
x 1
and bypass relays. Contact your local supplier for assistance with these tests.
Excess Start Time: Check load, increase Current Limit or adjust Excess Start Time setting.
x 2
Motor Overload: Allow motor to cool, reset soft starter and restart.
x 3
The soft starter cannot be reset until the motor has cooled.
Motor Thermistor: Check motor ventilation and thermistor connection TH1, TH2. Allow motor
x 4
to cool.
Current Imbalance: Check for mains supply or line current imbalance (L1, L2, L3).
x 5
Supply Frequency: Check mains voltage is available and supply frequency is in range.
x 6
Phase Sequence: Check for correct phase sequence.
x 7
Network Communication Failure (between module and network): Check network
x 8
connections, settings and configuration.
Starter Communication Failure (between starter and module): Remove and refit accessory
x 9
module.
Bypass Overload: Starter rating may be too low for the application.
x 10
6.3
Reset
Trips can be cleared by pressing the Reset button on the soft starter, sending a Reset command from the
serial communications network, or by switching the control inputs.
To clear a trip via the control inputs, the soft starter requires a closed to open transition on the stop input
(DI2).
In three-wire control, use the external stop pushbutton to momentarily open the stop input (open
CSL-DI2).
In two-wire control, if the soft starter tripped with a start signal present, remove the start signal (open
CSL to DI1, DI2).
In two wire control, if the Digistart CS tripped with no start signal present (e.g. Digistart CS motor
thermistor trip), apply then remove the start signal (close then reopen CSL to DI1, DI2).
The Reset button is located on the front of the unit, above the adjustment switches.
The soft starter will trip again immediately if the cause of the trip still exists.
Digistart CS User Guide
Issue: 2
Mechanical
Electrical
Installation
Installation
LED
Status
Off
No control power
On
Ready
Flash
Starter tripped
www.controltechniques.com
Programmable
Diagnostics
Parameters
Ready
Motor not running
Motor running at full speed
Motor starting or stopping
Description
Technical Data
Options
Run
15