AERMEC DUALCHILLER CONTROL Instalación Y Uso página 18

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

7. 1
READ ANALOG DATA
ADDRESS
DATA ITEM
1
ColdSet
2
SetCaldo
3
Tot.Diff.
4
S.Hot R
5
D.Tot. R
6
2nd C. Set
7
2nd H. Set
8
CP1 hours
9
CP1A hours
10
CP1B hours
11
CP2 hours
12
CP2A hours
13
CP2B hours
14
CP3 hours
15
CP3A hours
16
CP3B hours
17
CP4 hours
18
CP4A hours
19
CP4B hours
20
TIA "MASTER"
21
TIA "SLAVE"
22
TUA "MASTER"
23
TUA "SLAVE"
24
TAE "MASTER"
25
TAE "SLAVE"
26
TL 1
27
TL 2
28
TL 3
29
TL 4
30
TIAH "MASTER"
31
TIAH "SLAVE"
32
TUAH 1
33
TUAH 2
34
TUAH 3
35
TUAH 4
36
TIR "MASTER"
37
TIR "SLAVE"
38
TUR 1
39
TUR 2
40
TUR 3
41
TUR 4
42
TEV 1
43
TEV 2
44
TEV 3
45
TEV 4
46
TAC "MASTER"
47
TAC "SLAVE"
48
TFC "MASTER"
49
TFC "SLAVE"
50
PA 1
51
PA 2
52
PA 3
18
DESCRIPTION
Cold operating mode set
Hot operating mode set
Total differential set for thermostat
Hot operating mode recuperator control set
Total differential set for recuperator control thermostat
Second cold set
Second hot set
Circuit 1 compressor working hours
Circuit 1A compressor working hours
Circuit 1B compressor working hours
Circuit 2 compressor working hours
Circuit 2A compressor working hours
Circuit 2B compressor working hours
Circuit 3 compressor working hours
Circuit 3A compressor working hours
Circuit 3B compressor working hours
Circuit 4 compressor working hours
Circuit 4A compressor working hours
Circuit 4B compressor working hours
"MASTER" water inlet temperature
"SLAVE" water inlet temperature
"MASTER" water outlet temperature
"SLAVE" water outlet temperature
"MASTER" external air temperature
"SLAVE" external air temperature
Circuit 1 fluid temperature
Circuit 2 fluid temperature
Circuit 3 fluid temperature
Circuit 4 fluid temperature
"MASTER" (NLW) condenser inlet water temperature
"SLAVE" (NLW) condenser inlet water temperature
Circuit 1 (NLW) condenser outlet water temperature
Circuit 2 (NLW) condenser outlet water temperature
Circuit 3 (NLW) condenser outlet water temperature
Circuit 4 (NLW) condenser outlet water temperature
"MASTER" recovery exchanger inlet water temperature
"SLAVE" recovery exchanger inlet water temperature
Circuit 1 recovery exchanger outlet water temperature
Circuit 2 recovery exchanger outlet water temperature
Circuit 3 recovery exchanger outlet water temperature
Circuit 4 recovery exchanger outlet water temperature
Circuit 1 evaporator outlet gas temperature
Circuit 2 evaporator outlet gas temperature
Circuit 3 evaporator outlet gas temperature
Circuit 4 evaporator outlet gas temperature
"MASTER" storage water temperature
"SLAVE" storage water temperature
"MASTER" freecooling battery inlet water temperature
"SLAVE" freecooling battery inlet water temperature
High pressure circuit 1
High pressure circuit 2
High pressure circuit 3