Removable front
access panel
Position fork lift
under pallet
For final positioning with pallet
removed, fork lift points are under
the transformer. Forks must be
inserted all the way through the
depth.
Recommended cable
entry location (both
sides). Refer to
outline drawing for
exact dimensions.
Removable front
access panel
Position fork lift
For final positioning with pallet
under pallet
removed, fork lift points are under
the transformer. Forks must be
inserted all the way through the
depth.
Installation, Operation, and Maintenance Guide - Low Voltage Transformers
Cable entrance knockouts
(2 per side)
FIGURE 3
Typical Type 3R, NH Series Ventilated Enclosure Assembly
for Three Phase and Single Phase Transformers.
Notes:
1. Handling - units are designed to be raised by a fork lift
from underneath the pallet. Final positioning of the unit
with the pallet removed can be via a fork lift under the
transformer with the forks between the channels.
2. Shipping - units are shipped on pallets which are to be
removed at installation.
3. Installation - This transformer can be installed indoor or
outdoor providing a degree of protection against falling
rain, sleet and external ice formation.
4. All general purpose/drive isolation transformers should be
located away from any wall or any other obstruction,
please refer to the nameplate for the minimum distance.
5. DO NOT block bottom ventilation area
FIGURE 4
Typical Type 3R, NJ Series Ventilated Enclosure Assembly
for Three Phase or Single Phase Transformers.
Notes:
1. Handling - units are designed to be raised by a fork lift
from underneath the pallet. Final positioning of the unit
with the pallet removed can be via a fork lift under the
transformer with the forks between the channels. (Note:
Transformers weighing greater than 2350 lbs. should
be lifted by removing the top panel and accessing
the lifting provisions on top of the top of the core
and coil.)
2. Shipping - units are shipped on pallets which are to be
removed at installation.
3. Installation - This transformer can be installed indoor or
outdoor providing a degree of protection against falling
rain, sleet and external ice formation.
4. All general purpose/drive isolation transformers should be
located away from any wall or any other obstruction,
please refer to the nameplate for the minimum distance.
(Note: These enclosures are not intended to be wall
mounted. They may be mounted on a customer supplied
platform.)
5. DO NOT block bottom ventilation area.
18