3.1.
Further parameters
Parameters must be changed by qualified personnel.
In order to adjust ambient probes to the room where they are installed, it is necessary to comply with certain parameters.
PARAMETER AND DESCRIPTION
P51 Triggering temperature differential OFF for zone 1:
Switches the system off when the room temperature exceeds this value.
P52 Triggering temperature differential ON for zone 1:
Switches the system on when the room temperature exceeds this value.
P53 Ambient temperature probe correction range that can be set via
parameter for zone 1:
Corrects the value read by the probe
P54 Triggering temperature differential OFF for zone 2:
Switches the system off when the room temperature exceeds this value.
P55 Triggering temperature differential ON for zone 2:
Switches the system on when the room temperature exceeds this value.
P56 Ambient temperature probe correction range that can be set via
parameter for zone 2:
Corrects the value read by the probe.
º
3s
º
POSSIBLE VALUES
0.0 ÷ 1.0 °C
-1.0 ÷ -0.1 °C
-5.0 ÷ +5.0 °C
0.0 ÷ 1.0 °C
-1.0 ÷ -0.1 °C
-5.0 ÷ +5.0 °C
DEFAULT
0 °C
-0.5°C
0 °C
0 °C
-0.5°C
0 °C