2.4.7
Multimaster function
The Multimaster function can control up to six connected cooling units (bus functions). It regulates the cooling
mode as follows:
The first cooling unit that reaches the "TSet + 2K" switching threshold activates cooling mode in the bus
function.
The cooling mode is ended by the last unit that undercuts the switching threshold "TSet - 2K".
Energy-saving mode is ended by the cooling command of one of the cooling units in bus function.
Energy-saving mode is re-activated 30 minutes (condition as supplied) after the last cooling command of one of
the cooling units in the bus function.
All cooling units in the bus function can activate or end cooling mode or energy-saving mode. There is no
"master and slave function".
For electrical connection, see
Operating Manual DTS and DTI 6201 / 6301 Multi-Controller (MC) 086100010 © Pfannenberg GmbH
Figure 6 – Multimaster control
Multimaster
connection.