6. Setting of ʻSW_STEPʼ
n Use the ʻSW_SETPʼ to set a control step for contact signal
input.
: The type of input signal and control step can be set using ʻSW_STEPʼ
SW_STEP
- Type of input signal
SW_STEP
0, 1, 2, 3, 4, 5, 6
D
- Detail of the control step for contact signal input
SW_ STEP
Input_1
0
1
0
0
0
0
1
1
0
0
0
1
2
0
0
Contact signal input
Analog input signal
Input_2
Input_3
0
0
0
0
1
0
0
1
0
0
0
0
1
0
0
1
0
0
0
0
1
0
0
1
Setting and using method
Input Signal
Comp capacity
Of outdoor unit(%)
No control
70
40
COMP OFF
No control
70
50
COMP OFF
No control
80
50
COMP OFF
Installation manual 15
Type of input
Contact signal
Contact signal
Contact signal