Connect the signal cable from the controller to the input marked PWM / 10 V / 20
mA In (terminals 1 / 2).
If the signal cable carries low voltage (On / Off
phase control, trailing edge phase control) connect the cable to the low voltage
input of the device:
R In N max. 240 V (7) = neutral conductor N from the controller
R In L max. 240 V (8) = 230 V control signal from the controller (conductor L)
Note:
The corresponding input signal type has also to be adjusted by means of the
selector switch (see chap. 3.1).
Depending on the desired signal type, connect the output signal cable to GND (3)
and one of the following outputs:
10 V Out (4)
= 0-10 V control signal for the HE pump
ATTENTION!
Malfunction!
Pumps with line break detection run with minimum speed if the
control signal is 0 V.
Î Do not operate pumps with line break detection by
a 0-10 V signal!
PWM Out (5) = PWM control signal for the HE pump (via DIP switch 2 invertible)
20 mA Out (6) = 0-20 mA control signal for the HE pump (via DIP switch 4 con-
vertible to 4-20 mA, via DIP switch 2 invertible)
Power supply for the pump, connect the cable to the R Out relay output:
N (11)
= neutral conductor N pump
R Out L (9)
= 230 V power supply of the pump via the relay output (conductor L)
⌯ (12 / 13)
= grounding terminals
The mains connection of the device is at the following terminals:
N (14)
= neutral conductor N
L (15)
= conductor L
⌯ (12 / 13)
= grounding terminals
L' (10)
= conductor L' (L' not connected with the mains cable. L' is a
fused contact permanently carrying voltage)
DE-45527 Hattingen
14
burst / wave packets, leading-edge
,
PSW Universal
0
WARNING!
Electric shock!
L' is a fused contact permanently carrying voltage.
Î Always disconnect the controller from power supply
before opening the housing!
Attach flexible cables to the housing with the en-
closed strain relief and the corresponding screws.
2.3
Application example
1 2
3
4 5
6
PSW Universal
Controller
R-Out 1 (1) A (100 ... 240) V~
7
8
9
10
11
12 / 13 14 15
R-Out 1 (1) A (100 ... 240) V~
100 ... 240 V~
50-60 Hz
Mains connection
Input signal: 230 V control
signal from the controller
(On / Off, burst / wave packet,
phase cutting)
T2A
100 ... 240 V~
50-60 Hz
T4A
230V~