Installation
4
Connect Drain
Off-Line Vent (Type A or O): Connect 1-1/2" P-Trap and
drain piping (supplied by installer) to the drain spud .
Centrally Rising Vent (Type B or H) or models with
optional paper towel dispensers: Connect the vented
P-Trap (provided) and drain piping as shown:
5
Turn on Water and Electricity, Test and Adjust Unit
A
Turn on power to transformer . The solenoids will buzz
when a sensor is activated . If no buzz, check wiring .
Check to make sure stop valves are open
before turning on water.
Bradley • 215-1760 Rev. L; ECN 14-00-007
Strainer
Drain Spud
Tailpiece
P-Trap
B
Turn on water supply and check for leaks . Activate
each TT Sensor to purge air from the lines .
C
H
Pipe (supplied by
Loosen the cap screw about
C
¼" (4–6 turns) and lift up
the cover (do not remove) .
This valve is NOT factory preset. Upon
installation, the temperature of this
valve must be checked and adjusted
to ensure delivery of a safe water
temperature. Water in excess of 110°F
(43°C) may cause scalding.
Using the cover, turn
the cartridge gently until
desired water temperature
D
is reached . Do not turn past
stops as this may damage
the unit . Push the cover
down and tighten the screw .
10/20/2014
SN2005/TT
1-1/2" NPT Vent
installer)
1-1/2" NPT Tee
1-1/2" NPT Close
Nipple
1-1/2" Drain
(supplied by
installer)
7