Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 25
Symptom
Fault code is shown as 14 and
alarm is continuously sounding.
Fault code is shown as 01, 02, 03,
11, 12, 13 and 41 on LCD display
and
alarm
is
sounding.
Battery backup time is shorter
than nominal value
Fault code is shown as 45 on LCD
display. At the same time, alarm is
continuously sounding.

5. Storage and Maintenance

Operation
The UPS system contains no user-serviceable parts. If the battery service life (3~5 years at
25°C ambient temperature) has been exceeded, the batteries must be replaced. In this
case, please contact your dealer.
Be sure to deliver the spent battery to a recycling facility or ship it to your
dealer in the replacement battery packing material.
Storage
Before storing, charge the UPS 5 hours. Store the UPS covered and upright in a cool, dry
location. During storage, recharge the battery in accordance with the following table:
Storage Temperature
-25°C - 40°C
40°C - 45°C
Possible cause
The UPS shut down
automatically because
short circuit occurs on the
UPS output.
A UPS internal fault has
occurred. There are two
continuously
possible results:
1. The load is still
supplied, but directly from
AC power via bypass.
2. The load is no longer
supplied by power.
Batteries are not fully
charged
Batteries defect
The charger does not have
output and battery voltage
is less than 10V/PC.
Recharge Frequency
Every 3 months
Every 2 months
Check output wiring and if
connected devices are in
short circuit status.
Contact your dealer
Charge the batteries for at
least 5 hours and then
check capacity. If the
problem still persists,
consult your dealer.
Contact your dealer to
replace the battery.
Contact your dealer.
Charging Duration
1-2 hours
1-2 hours
20
Remedy
EN

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

1500rm lcd2000rm lcd3000rm lcd

Tabla de contenido