Configuration Menu

Press the DHW buttons together for 10 seconds to access the configuration Menu. 8 parameters are available, indicated by the letter "b", which are not modifiable from Remote
Timer Control.
Press the Heating buttons to scroll the list of parameters in increasing or decreasing order. Press the DHW buttons to view or modify the value of a parameter: the modification will
be automatically saved.
Contents
Description
b01
Gas type selection
b02
Boiler type selection
b03
Combustion chamber type selection
Primary Exchanger type selection (b03=0)
No effect on adjustment (b03=1)
No effect on adjustment (b03=2)
b04
Primary Exchanger type selection (b03=3)
No effect on adjustment (b03=4)
No effect on adjustment (b03=5)
Auxiliary relay card (b02=1)
operation selection (b02=1)
b05
No effect on adjustment (b02=2)
No effect on adjustment (b02=3)
No effect on adjustment (b02=4)
b06
Mains Voltage Frequency
Comfort burner on time (b02=1)
No effect on adjustment (b02=2)
b07
No effect on adjustment (b02=3)
No effect on adjustment (b02=4)
b08
Driver Gas valve
Notes:
1.
Parameters with more than one description vary their function and/or range in relation to the setting of the parameter given in brackets.
2.
Parameters with more than one description are reset to the default value if the parameter given in brackets is modified.
To exit the configuration Menu press the DHW buttons together for 10 seconds, or exiting occurs automatically after 2 minutes.

Service menu

The card Service Menu is accessed by pressing the Reset button for 20 seconds. 4 submenus are available: press the Heating buttons to select, in increasing or decreasing order,
"tS", "In", "Hi" or "rE". "tS" means Transparent Parameters Menu, "In" means Information Menu, "Hi" means History Menu: after selecting the submenu, press the Reset button again
to access it; "rE" means History Menu Reset: see description.
"tS" - Transparent Parameters Menu
16 parameters indicated by the letter "P" are available: which are also modifiable from Remote Timer Control.
Press the Heating buttons to scroll the list of parameters in increasing or decreasing order. Press the DHW buttons to view or modify the value of a parameter: the modification will
be automatically saved.
Contents
Description
P01
Ignition ramp Offset
P02
Heating ramp
P03
Heating standby time
P04
Heating Post-Circulation
P05
Heating user max. set point
P06
Max. output in heating
Burner shutdown in hot water production (b02=1)
P07
Burner shutdown in hot water production (b02=2)
Hot water tank hysteresis (b02=3)
Hot water tank hysteresis (b02=4)
Range
0=Natural Gas
1=LPG
1=Bithermal instantaneous
2=Monothermal instantaneous
3=Heating only (3-way valve)
4=Heating only (circulating pump)
0=Sealed Chamber combustion control
(without fume pressure switch)
1=Open Chamber (with fume thermostat)
2=Sealed Chamber (with fume pressure switch)
3=Sealed Chamber combustion control (with fume thermostat on recuperator)
4=LOW NOx Sealed Chamber Combustion control (without fume pressure switch)
5=LOW NOx Open Chamber (with fume thermostat)
0=Flat
1=Omega
2=--
--
--
0=Flat
1=Omega
2=--
--
--
0=External gas valve
1=System filling solenoid valve
2=Solar 3-way valve
--
--
--
0=50Hz
1=60Hz
0-20 seconds
--
--
--
0 = Standard, 1
Range
0-40
1-20°C/minute
0-10 minutes
0-20 minutes
31-85°C
0-100%
0=Fixed
1=Linked to set point
2=Solar (5)
3=Solar (10)
4=Solar (20)
0=Fixed
1=Linked to set point
2=Solar (5)
3=Solar (10)
4=Solar (20)
0-4°C
0-4°C
cod. 3541F142 - Rev. 01 - 03/2018
Default
0=Natural Gas
1=Bithermal instantaneous
0=Sealed Chamber with
combustion control
0=Flat
0
0
0=Flat
0
0
0=External gas valve
0
0
0
0=50Hz
5 seconds
5
5
5
0=Standard
Default
20
5°C/minute
2 minutes
6 minutes
80°C
100%
0=Fixed
0=Fixed
2°C
2°C
FL 32 MCS
0=Natural Gas
2=Monothermal instantaneous
0=Sealed Chamber with
combustion control
(without fume pressure switch)
0=Flat
0=External gas valve
0=50Hz
5 seconds
0=Standard
FL 32 MCS
20
5°C/minute
2 minutes
6 minutes
80°C
100%
0=Fixed
EN
7