Example for a 230V/4kVA generator (3000 rpm):
A 4kVA/230V generator can supply a maximum current of 17,4A. Using the 70%
safety margin we will set the generator current limit to 12A. To set the
configuration, using either a 16A or 30A panel, do the following:
Press and hold the configuration button until the bottom LED in the left column
starts flashing indicating step 1.
This step can be ignored because we assume VE.Bus Multis.
Press the button to go to the next step.
(The lower left LED will turn on indicating step 2.)
Determine the value for step 2 by dividing the required generator current by 2.
12/2 = (0)6.
Because this is lower than 10 the value to be set during step 2 is 0.
The value to be set during step 3 is 6.
Turn the knob until all LEDs in the right columns are off. Setting the value for step
2 to 0.
Press the button to go to step 3.
Turn the knob until the bottom 3 LEDs in the right columns are on. Setting the
value for step 3 to 6.
Press the button to finalize the configuration.
7