Start-Up; Maintenance - Lamborghini Caloreclima ERA F 23 Instrucciones De Uso, Instalación Y Mantenimiento

Ocultar thumbs Ver también para ERA F 23:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

ERA F 23 - 32 - 45 - 56
Remote
Card
Description of transparent parameters
Control
19
P19
Not used
20
P20
Not used
21
P21
Not used
22
P22
Legionella protection
23
P23
Not used
24
P24
Mains Voltage Frequency
Press the Heating buttons to scroll the list of parameters in increasing or decreasing or-
der. Press the DHW buttons to modify the value of a parameter: the change will be au-
tomatically saved.
The Max. Heating Power and Lighting Power parameters can be modified in Test Mode
(see relevant section).
Press the Reset button to return to the Service Menu. Press the Reset button for 10 sec-
onds to exit to the card Service Menu.
"In" -Information menu
The card can display the following information:
t01
Heating NTC sensor (°C)
t02
DHW NTC sensor (°C)
t03
Safety NTC sensor (°C)
t04
External NTC sensor (°C)
L05
Actual burner power (%)
P06
Actual system water pressure (bar/10)
F07
Actual ionisation current (uA)
Press the Heating buttons to scroll the list of information. In case of damaged sensor,
the card displays hyphens.
Press the Reset button to return to the Service Menu. Press the Reset button for 10 sec-
onds to exit the Service Menu.
"Hi" - History menu
The card can store the last 10 faults: the History datum item H1: represents the most
recent fault that occurred; the History datum item H10: represents the least recent fault
that occurred.
The codes of the faults saved are also displayed in the corresponding menu of the Open-
therm remote control.
Press the Heating buttons to scroll the list of faults. Press the DHW buttons to display the
value.
Press the Reset button to return to the Service Menu. Press the Reset button for 10 sec-
onds to exit the Service Menu.
"rE" - History reset
Press the M button for 3 seconds to delete all the faults and times stored in the History
Menu: the card will automatically exit the Service Menu, in order to confirm the operation.
Press the Reset button to return to the Service Menu.

3.2 Start-up

B
Commissioning must be carried out by Qualified Personnel such as the staff of
our Sales Organisation and your local After-Sales Technical Service.
First lighting is free of charge and must be requested as indicated on the sticker
on the boiler.
Checks to be made at first lighting, and after all maintenance operations that involved
disconnecting from the systems or work on safety devices or parts of the boiler.
Before lighting the boiler
Open any on-off valves between the boiler and the systems.
Check the tightness of the gas system, proceeding with caution and using a soap
and water solution to detect any leaks in connections.
Check the correct preloading of the expansion tank (ref. sec. 4.3)
Fill the water system and make sure that all air contained in the boiler and the sys-
tem has been vented by opening the air vent valve on the boiler and any vent valves
on the system.
Make sure there are no water leaks in the system, hot water circuits, connections or
boiler.
Check the correct connection of the electric system and the functioning of the earth
system. l
Check that the gas pressure value for heating is as required.
Make sure there are no flammable liquids or materials in the immediate vicinity of
the boiler
Range
Default
Not modifiable
0
Not modifiable
4 bar/10
Not modifiable
8 bar/10
0-7
0
Not modifiable
0
0=50Hz
0=50Hz
1=60Hz
between 05 and 125 °C
between 05 and 125 °C
between 05 and 125 °C
between -30 and 70°C (Negative values flash)
00%=Min., 100%=Max.
00=Pressure switch open
14= Pressure switch closed
00=burner off
cod. 3540L893 - Rev. 01 - 03/2018
Boiler lighting
Open the gas cock ahead of the boiler.
Vent the air from the pipe ahead of the gas valve.
Turn on or insert any switch or plug ahead of the boiler.
If the display shows the message OFF, press the button M (detail 7 - fig. 1) for 5 sec-
onds.
Set the boiler to winter mode.
Adjust the heating temperature to a value above 50°C and the possible room ther-
mostat to the required temperature value. The burner will now light and the boiler
starts working automatically, controlled by its adjustment and safety devices.
B
If the burners do not light and the "block" indicator comes on after correctly car-
rying out the lighting procedures, wait approx. 15 seconds then press the button
R (detail 6 - fig. 1). The reset control unit will repeat the lighting cycle. If the
burners do not light after the second attempt, consult the section "Troubleshoot-
ing".
In case of a power failure while the boiler is working, the burners will go out and
A
automatically relight when power is restored.
Checks during operation
Ignite the appliance as described in sec. 1.3.
Check the airtightness of the fuel circuit and water systems.
Check the efficiency of the flue and air-fume ducts while the boiler is working.
Check that the water is circulating properly between the boiler and the systems.
Make sure that the gas valve modulates correctly in both the heating and hot water
production phases.
Check the proper ignition of the boiler by performing various tests, turning it on and
off with the room thermostat or remote control.
Make sure that the fuel consumption indicated on the meter corresponds to that giv-
en in the technical data table in sec. 4.3.
Make sure that with no call for heating the burner correctly ignites on opening a hot
water tap. Check that during heating operation, on opening a hot water tap, the heat-
ing circulator stops and there is a regular production of hot water.
Check the parameters are programmed correctly and perform any required custom-
ization (compensation curve, power, temperatures, etc.)

3.3 Maintenance

B
The following operations must only be carried out by Qualified Personnel.
Periodical check
To ensure proper operation of the unit over time, have qualified personnel carry out a
yearly check, providing for the following:
The control and safety devices (gas valve, flowmeter, thermostats, etc.) must func-
tion correctly.
The fume exhaust circuit must be perfectly efficient.
(Sealed chamber boiler: fan, pressure switch, etc. - The sealed chamber must be
tight: seals, cable glands, etc.)
(Open chamber boiler: anti-backflow device, fume thermostat, etc.)
The air/fume terminal and ducts must be free of obstructions and leaks
The burner and exchanger must be clean and free of deposits. For cleaning do not
use chemical products or wire brushes.
The electrode must be free of scale and properly positioned.
The gas and water systems must be tight.
The water pressure in the cold water system must be approx. 1 bar; otherwise bring
it to that value.
The circulating pump must not be blocked.
The expansion tank must be filled.
The gas flowrate and pressure must match that given in the respective tables.
The boiler casing, control panel and aesthetic parts can be cleaned with a soft
A
damp cloth, if necessary soaked in soapy water. Do not use any abrasive de-
tergents and solvents.
9
EN

Publicidad

Tabla de contenido

Solución de problemas

loading

Este manual también es adecuado para:

Era f 32Era f 45Era f 56

Tabla de contenido