Vibration Resistance: The test method shall be in accordance with
IEC 60068-2-6. The indicator shall be fastened to the vibrator by rigid
intermediate parts which shall not affect the test results. To attenuate
any large amplitude oscillations which may be induced in the contact
electrode during the test, the free end of the electrode shall be fastened
to the rigid part.
The amplitude and acceleration shall be as follows:
0,15mm peak value between 10 Hz and 58Hz;19.6 m/s2 peak value
between 58Hz and 150 Hz.
The duration of the tests shall be set for 2 h in each direction.
The test is considered passed if the detector shows no apparent
mechanical deterioration.
Shock Resistance: In accordance with IEC 61243-1 Test 6.4.5.
Five mechanical shocks are performed on the most fragile parts of the
indicator.
The test is passed if the indicator shows no incipient fracture.
Cleaning Kit:
95mm
27mm
Acetal/Steel
85mm
25mm
Acetal/Steel
85mm
45mm
Acetal/Steel
1200mm total
Fibreglass
Cloth and bottles of polymer liquid