Malfunctions caused by residues.
Proper functioning is not guaranteed.
Visually check that there are no metal chips or other residues in the connections.
It is important that metal chips or other residues are blown out.
Install with suitable tools, if required.
Regarding screw connections, use a second spanner to brace against the connection nozzle.
Do not use unsuitable tools, such as pliers.
Option assembly metal filter tray PS 16bar instead of plastic filter tray
• Loosen the clamping ring
• Do not damage the O-ring, refurbish if required (oil new O-ring!)
• Fit the metal filter tray and the O-ring and manually tighten by rotating the clamping ring
in a clockwise direction
• Perform leak testing activities!

LEAK CHECK

Check the condition of the system:
• before initial start-up,
• after major changes,
• after repairs,
• after the system has been out of operation for more than one year.
Check the system with 1.1 x the operating pressure using air or an inert gas. The system is
leakproof if the test pressure does not drop after 10 minutes.
Prior to start-up, the oil system with GS Pro-Fi
subjected to leak testing. This may be performed within the framework of leak testing
pursuant to TRÖI and worksheet DWA-A 791, as well as function check of the oil system.
In the event of possible leaks, these must be eliminated, e.g. repeated assembly of the
connections using new gaskets, tightening of the screwed connections.
Observe the notice in MAINTENANCE!
NOTICE FOR LEAK TESTING
We recommend using the vacuum test device
type UPE-300 item no. 13 602 00 for leak testing.
NOTICE
Please find comprehensive information on leak testing pursuant to TRÖI and
worksheet DWA-A 791 on the Internet.
8 / 16
Combined heating oil filter breather type GS Pro-Fi
by anti-clockwise rotation, hold and remove the filter tray
3, including the connections, must be
®
Pursuant to TRÖl chapter 4.10.4.2. "Vacuum
leak testing", the test time is:
• 10 minutes plus the time required for
The oil line is deemed tight if the pressure
increase during the specified test time is not
higher than 30mbar. If this requirement is not
met, the leak must be found applying a slight
over-pressure and foam-forming substances
and the error must be eliminated. Thereafter,
the oil system must be re-checked.
for oil systems pursuant to TRÖl
temperature equalisation.
®
3
Item No. 13 512 53