Panel Mounting
Standard Panel
Front View
Wiring raceway
Feed
wiring
(top
entry)
Max. Heat
BTUs (Kcal)
Panel
per Hour
DCI1
260 (65.56)
DCI2
515 (129.86)
DCI3
770 (194.17)
*Packaging weight adds 50 lbs (23 kg).
4 Installation Guide for DCI Dimming Panels
Side View
Load
12 in.
wiring
(305 mm)
(top
min.
entry)
PELV (Class
2: USA)
wiring to
controls
12 in. (305 mm)
Air flow
min. clearance
Wall
Max. Weight w/o
Packaging*
pounds (kg)
130 (59)
170 (77)
210 (95)
Mounting Guidelines
• For Indoor Use Only! NEMA, Type 1 enclosure, IP20.
• Panel generates heat. Mount where ambient
temperature is 32-104 ºF (0-40 ºC).
• Relative humidity must be <90% non-condensing.
• Reinforce wall structure for panel weight and local
codes; see table.
• Mount panel where audible noise is acceptable
(internal relays click).
• Mount panel so line (mains) voltage wiring is at least 6
ft. (1.8 m) from audio or electronic equipment and
associated wiring.
• Mount within 7º of true vertical.
• Panel clearances are 12 in. (305 mm) above and
below and 0 in. to each side. Allow room for PELV
(Class 2: USA) clearance.
Caution! This equipment is air-cooled.
Vents must not be blocked or you will
void the warranty.