XC1:13
(24 Vdc)
XC1:11
RL ≥ 500 Ω
(DGND*)
(-)
Power Supply
20...30 Vdc
(+)
* It is possible to insert the accessory on slots 1 and 2 on the PLC300. The digital inputs and outputs are represented by DI10X/DO10X
(Slot 1) and DI20X/DO20X (Slot 2).
Figure 8: IOC-03 – XC17 Terminal strip – Digital inputs as active high
XC17
PLC300(*)
1
DI9
DI101/DI201
2
DI10
DI102/DI202
3
DI11
DI103/DI203
4
DI12
DI104/DI204
5
DI13
DI105/DI205
6
DI14
DI106/DI206
7
DI15
DI107/DI207
8
DI16
DI108/DI208
9
COM
COM
10
DO6
DO101/DO201 Transistor Output 6
11
DO7
DO102/DO202 Transistor Output 7
12
DO8
DO103/DO203 Transistor Output 8
13
DO9
DO104/DO204 Transistor Output 9
14
DO10 DO105/DO205 Transistor Output 10
15
DO11 DO106/DO206 Transistor Output 11
16
DO12
DO107/DO207 Transistor Output 12
17 GNDBB
GNDBB
18
VBB
VBB
Installation, Configuration and operation guide
Function
Digital Input 9
Digital Input 10
Digital Input 11
Digital Input 12
Digital Input 13
Digital Input 14
Digital Input 15
Digital Input 16
Common point of
the digital inputs
0 V digital output
(20...30 Vdc) for
digital outputs
Specifications
8 isolated digital inputs
High level ≥ 18 V
Low level ≤ 3 V
Input voltage ≤ 30 V
Input current: 11 mA @
24 Vdc
7 isolated digital outputs,
protected, PNP
Maximum 20...30 V
Maximum current: 500 mA