WEG IOC-01 Guía De Instalación, Configuración Y Operación página 9

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

XC1:13
(24 Vdc)
XC1:11
R
≥ 500 Ω
L
(DGND*)
* It is possible to insert the accessory on slots 1 and 2 on the PLC300. The digital inputs and outputs are represented by DI10X/DO10X
(Slot 1) and DI20X/DO20X (Slot 2).
Figure 6: IOC-02 – XC16 Terminal strip – Digital inputs as active high
XC16
PLC300(*)
1
DI9
DI101/DI201
2
DI10
DI102/DI202
3
DI11
DI103/DI203
4
DI12
DI104/DI204
5
DI13
DI105/DI205
6
DI14
DI106/DI206
7
DI15
DI107/DI207
8
DI16
DI108/DI208
9
COM
COM
10
DO6
DO101/DO201 Transistor Output 6
11
DO7
DO102/DO202 Transistor Output 7
12
DO8
DO103/DO203 Transistor Output 8
13
DO9
DO104/DO204 Transistor Output 9
14
DO10 DO105/DO205 Transistor Output 10
15
DO11 DO106/DO206 Transistor Output 11
16
DO12
DO107/DO207 Transistor Output 12
17
DO13 DO108/DO208 Transistor Output 13
18 24 Vdc
24 Vcc
Installation, Configuration and operation guide
Function
Digital Input 9
Digital Input 10
Digital Input 11
Digital Input 12
Digital Input 13
Digital Input 14
Digital Input 15
Digital Input 16
Common point of the
digital inputs
24 Vdc power suply
Specifications
8 isolated digital inputs
High level ≥ 18 V
Low level ≤ 3 V
Input voltage ≤ 30 V
Input current: 11 mA @
24 Vdc
8 isolated digital outputs,
open collector with
freewheel diode
Maximum voltage: 24 V
Maximum current: 50 mA
24 Vdc power suply, ± 8 %.
Capacity: 500 mA