Features
Network Interface
A
Ethernet Port: RJ45 jack connects the PDU's Network Interface to the network
using a standard Ethernet patch cable. LEDs
conditions (shown in the table below).
B
RJ45 Configuration Port: Use this port to provide a direct terminal connection
to a computer with a terminal emulation program. An RJ45 to DB9 cable (part
number 73-1243) is included with the PDU. To request a replacement cable,
visit www.tripplite.com for ordering information.
C
USB Type-A Port: Use this port to connect up to three linked Tripp Lite
EnviroSense2 modules (E2MT, E2MTDO, E2MTDI, E2MTHDI) for a variety of
environmental monitoring and control options. See www.tripplite.com for more
information about these modules.
Note: Do not connect a keyboard or mouse to this port.
D
Reset Button: Accessible through a small hole on the faceplate above the RJ45
Configuration Port. Press once to reset the Network Interface. Press and hold for
15 seconds to reset the Network Interface to factory default settings.
Note: PDU loads will not be affected.
E
Status LED: Shows the Network Interface status (shown in the table below).
Identifier LED Function
Ethernet Link/
A1
Activity Indicator
Ethernet
A2
Network Speed
Indicator
Network
E
Interface Status
17-02-374-9336CB.indb 6
E
D
B
LED Color Status
Green
Flashing
Off
Yellow
On steady
Off
Off
Green
On steady
Single flash
Green/
Off
Orange
Alternating (~1/sec.) Software update in progress
Alternating (~2/sec.) Restoring factory default
A2
A1
C
A
and
indicate the operating
A1
A2
Description
There is network activity on the
port
There is no network activity on
the port
100 Mbps network speed
10 Mbps speed if A1 is flashing
No network activity if A1 is also
off
Normal operation
Power up indicator
No power or card is initializing
configuration