1. Important Safety Instructions SAVE THESE INSTRUCTIONS • This manual contains instructions and warnings that should be followed during the installation, operation and storage of this product. Failure to heed these instructions and warnings may affect the product warranty. • Warning: This equipment is compliant with Class A of CISPR 32. In a residential environment, this equipment may cause radio interference.
Página 3
1. Important Safety Instructions • Only those who are properly trained or qualified to use this device should do so. Anyone who is not trained or qualified should not use this device unless it is under the supervision of someone who is properly trained or qualified to do so.
2. Installation 2.1 Mounting the PDU The PDU supports 1U Rack configurations. Note: The user must determine the fitness of hardware and procedures before mounting. The PDU and included hardware are designed for common rack and rack enclosure types and may not be PDUMH15HVAT, PDUMH15HVATNET appropriate for all applications.
Página 5
2. Installation Feature Set Overviews Outlet Shipped Shipped with Outlet with SNMP SNMP Card Part Description Types Outlet Control Indicator Slot Installed PDUMH15HVAT PDUMH15HVATNET PDUMH20HVAT C13, C19 YES (C13 Only) YES PDUMH20HVAT1 C13, C19 YES (C13 Only) YES PDUMH20HVATNET C13, C19 YES (C13 Only) YES PDUMNH20HVAT1 C13, C19...
2. Installation 2.2.2 Connect PDU Input Plugs: (See the Configuration and Operation section for more information.) Connect the Primary input plug to a preferred source of grounded 230V AC power, such as a SmartOnline UPS System. ® The UPS system must not share a circuit with a heavy electrical load (such as an air conditioner or refrigerator).
3. Features PDUMH15HVAT, PDUMH15HVATNET PDUMH20HVAT, PDUMH20HVATNET, PDUMH20HVAT1 PDUMH20HVATS, PDUMNH20HVAT1 *Models with SNMP card installed only.
Página 8
3. Features Primary Input Models PDUMH15HVAT/NET: The C13-C14 cord is detachable. Models PDUMH20HVAT, PDUMH20HVAT1, PDUMH20HVATS, PDUMNH20HVAT1, PDUMH20HVATNET: The C19-C20 cord is detachable. Secondary Input Inlet (detachable on all models) Models PDUMH15HVAT/NET: The IEC-320-C14 inlet connects to the detachable Secondary AC Input Power Cord. Models PDUMH20HVAT, PDUMH20HVAT1, PDUMH20HVATS, PDUMNH20HVAT1, PDUMH20HVATNET: The IEC-320-C20 inlet connects to the detachable Secondary AC Input Power Cord.
Página 9
3. Features Primary and Secondary AC Input Power Cord (Models PDUMH20HVAT, PDUMH20HVAT1, PDUMH20HVATNET, PDUMH20HVATS, PDUMNH20HVAT1): Two C19-C20 cables are included: one for Primary Input and one for Secondary Input. Primary AC Input Power Cord (Models PDUMH15HVAT, PDUMH15HVATNET): A C13-C14 cable is included.
4. Configuration and Operation 4.1 Automatic Transfer Switch When the Primary and Secondary inputs are both connected to Tripp Lite UPS Systems, the PDU operates as an Automatic Transfer Switch, providing redundant input power for high availability applications. Under normal operating conditions, the PDU will distribute power from the Primary input source, switching to the Secondary input source under certain conditions.
4. Configuration and Operation 4.1.2 Automatic Transfer Switch Source Selection The PDU will power up if one of the input sources is greater than the minimum startup voltage. In normal operation (after power-up), if the presently selected source (primary or secondary) degrades to a lesser condition, the unit should switch to the alternate source, if that source is of better quality.
5. Warranty and Product Registration 2-Year Limited Warranty Seller warrants this product, if used in accordance with all applicable instructions, to be free from original defects in material and workmanship for a period of two (2) years from the date of initial purchase. If the product should prove defective in material or workmanship within that period, Seller will repair or replace the product, at its sole discretion.
Manual del Propietario PDU para Instalación en Rack con Medidor Digital y Switch de Transferencia Automática Modelos: PDUMH15HVAT, PDUMH15HVATNET, PDUMH20HVAT, PDUMH20HVAT1, PDUMH20HVATNET, PDUMH20HVATS, PDUMNH20HVAT1 Número de serie: AGAC7625 1. Instrucciones de Seguridad Importantes 2. Instalación 2.1 Instalación del PDU 2.2 Conexión del PDU 2.3 Conexión a Red del PDU 3.
1. Instrucciones de Seguridad Importantes CONSERVE ESTAS INSTRUCCIONES • Este manual contiene instrucciones y advertencias que deben seguirse durante la instalación, operación y almacenamiento de este producto. El incumplimiento de estas instrucciones y advertencias puede afectar la garantía del producto. •...
Página 15
1. Instrucciones de Seguridad Importantes • Las clavijas en los cables de alimentación y la entrada del aparato sirven como los dispositivos de desconexión. Asegúrese de que los tomacorrientes que alimentan al PDU sean fácilmente accesibles. • Este equipo no es adecuado para uso en ubicaciones donde es probable que estén presentes niños.
2. Instalación 2.1 Instalar el PDU el PDU es compatible con configuraciones de 1U de rack. Nota: Antes de la instalación, el usuario debe determinar la conveniencia de los accesorios y procedimientos. El PDU y los accesorios incluidos PDUMH15HVAT, PDUMH15HVATNET están diseñados para tipos comunes de racks y gabinetes y pueden no ser apropiados para todas las aplicaciones.
2. Instalación Descripción General del Conjunto de Características Tipos de Control de Indicador Se Embarca Se Embarca con Descripción de la Tomacor- Tomacor- LED de con Ranura Tarjeta SNMP Parte riente rientes Salida SNMP Instalada PDUMH15HVAT SÍ SÍ SÍ PDUMH15HVATNET SÍ...
2. Instalación 2.2.2 Conecte las Clavijas de Entrada del PDU: (Para más información, consulte la sección de Configuración y Operación.) Conecte la clavija de entrada Primaria a una fuente preferente de alimentación de 230V CA conectada a tierra, como un Sistema UPS SmartOnline .
Página 20
3. Características Modelos de Entrada Primaria PDUMH15HVAT/NET: El cable C13-C14 es desprendible. Modelos PDUMH20HVAT, PDUMH20HVAT1, PDUMH20HVATS, PDUMNH20HVAT1, PDUMH20HVATNET: El cable C19-C20 es desprendible. Entrada Secundaria (desprendible en todos los modelos) Modelos PDUMH15HVAT/NET: La entrada IEC-320-C14 se conecta al cable de alimentación de CA Secundario desprendible. Modelos PDUMH20HVAT, PDUMH20HVAT1, PDUMH20HVATS, PDUMNH20HVAT1, PDUMH20HVATNET: La entrada IEC-320-C20 se conecta al cable de alimentación de CA Secundario desprendible.
Página 21
3. Características Cable de Alimentación de CA Primaria y ecundaria (Modelos PDUMH20HVAT, PDUMH20HVAT1, PDUMH20HVATNET, PDUMH20HVATS, PDUMNH20HVAT1): Se incluyen dos cables C19-C20: uno para entrada primaria y uno para entrada secundaria. Cable de Alimentación de Entrada Primaria de CA (Modelos PDUMH15HVAT, PDUMH15HVATNET): Se incluye un cable C13-C14.
4. Configuración y Operación 4.1 Switch de Transferencia Automática Cuando las entradas Primaria y Secundaria están ambas conectadas a los sistemas de UPS de Tripp Lite, el PDU opera un Switch de Transferencia Automática que proporciona energía redundante de entrada para aplicaciones de alta disponibilidad. Bajo condiciones de operación normales, el PDU distribuirá...
4. Configuración y Operación 4.1.2 Selección de la Fuente del Switch de Transferencia Automática El PDU se encenderá si una de las fuentes de entrada es mayor que el voltaje mínimo de inicio. En operación normal (después del encendido), si la fuente seleccionada en ese momento (Primaria o Secundaria) se degrada a una condición menor, la unidad debe cambiar a la fuente alternativa, si esa fuente es de mejor calidad.
5. Garantía Garantía Limitada por 2 Años El vendedor garantiza que este producto, si se usa de acuerdo con todas las instrucciones correspondientes, no presentará defectos originales en cuanto a materiales y mano de obra durante dos (2) años contados desde la fecha de compra inicial.
Manuel de l'utilisateur PDU pour montage en bâti muni d'un compteur avec commutateur de transfert automatique Modèles : PDUMH15HVAT, PDUMH15HVATNET, PDUMH20HVAT, PDUMH20HVAT1, PDUMH20HVATNET, PDUMH20HVATS, PDUMNH20HVAT1 Numéro de série : AGAC7625 1. Consignes de sécurité importantes 2. Installation 2.1 Montage de la PDU 2.2 Raccordement de la PDU 2.3 Fonctionnement en réseau de la PDU 3.
1. Consignes de sécurité importantes CONSERVER CES INSTRUCTIONS • Ce manuel contient des instructions et des avertissements qui doivent être respectés pendant l'installation, l'utilisation et l'entreposage de ce produit. Le non-respect de ces instructions et avertissements pourrait nuire à la garantie du produit. •...
Página 27
1. Consignes de sécurité importantes • Les fiches sur les cordons d'alimentation et l'entrée de l'appareil servent de dispositifs de déconnexion. S'assurer que les prises de courant fournissant l'alimentation à la PDU sont facilement accessibles. • Cet équipement ne convient pas à une utilisation dans des endroits où des enfants risquent d'être présents.
2. Installation 2.1 Montage de la PDU La PDU peut accueillir les configurations en bâti 1U. Remarque : L'utilisateur doit déterminer l'aptitude de la quincaillerie et des procédures avant le montage. La PDU et le matériel inclus sont conçus pour les PDUMH15HVAT, PDUMH15HVATNET bâtis et les boîtiers pour bâtis communs et peuvent ne pas être appropriés pour toutes les applications.
Página 29
2. Installation Aperçus de l'ensemble des fonctionnalités Expédiée Voyant à Expédiée avec une Description des Types de Contrôle de la DEL de avec une carte SNMP pièces sortie prise sortie fente SNMP installée PDUMH15HVAT PDUMH15HVATNET OUI (C13 PDUMH20HVAT C13, C19 seulement) OUI (C13 PDUMH20HVAT1...
2. Installation 2.2.2 Raccorder les fiches d'entrée de la PDU : (Consulter la section Configuration et fonctionnement pour de plus amples informations.) Raccorder la fiche d'entrée principale à une source préférentielle d'alimentation de 230 V CA mise à la terre, comme un onduleur SmartOnline .
3. Caractéristiques PDUMH15HVAT, PDUMH15HVATNET PDUMH20HVAT, PDUMH20HVATNET, PDUMH20HVAT1 PDUMH20HVATS, PDUMNH20HVAT1 *Modèles sur lesquels une carte SNMP est installée seulement.
Página 32
3. Caractéristiques Entrée principale Modèles PDUMH15HVAT/NET : Le cordon C13-C14 est amovible. Les modèles PDUMH20HVAT, PDUMH20HVAT1, PDUMH20HVATS, PDUMNH20HVAT1, PDUMH20HVATNET : Le cordon C19-C20 est amovible. Entrée secondaire (amovible sur tous les modèles) Modèles PDUMH15HVAT/NET : L'entrée IEC-320-C14 se connecte au cordon d'alimentation d'entrée CA secondaire amovible.
Página 33
3. Caractéristiques Cordon d'alimentation d'entrée CA principal et secondaire (modèles PDUMH20HVAT, PDUMH20HVAT1, PDUMH20HVATNET, PDUMH20HVATS, PDUMNH20HVAT1) : Deux câbles C19-C20 sont inclus : un pour l'entrée principale et l'autre pour l'entrée secondaire. Cordon d'alimentation d'entrée CA principal (modèles PDUMH15HVAT, PDUMH15HVATNET) : un cordon C13- C14 est inclus.
4. Configuration et fonctionnement 4.1 Commutateur de transfert automatique Lorsque les entrées principale et secondaire sont toutes les deux raccordées aux onduleurs Tripp Lite, la PDU fonctionne comme un commutateur de transfert automatique, fournissant de l'alimentation d'entrée redondante pour les applications à disponibilité élevée. Dans des conditions de fonctionnement normales, la PDU va distribuer de l'alimentation depuis la source d'entrée principale et commuter à...
Página 35
4. Configuration et fonctionnement 4.1.2 Sélection de la source pour le commutateur de transfert automatique La PDU va démarrer si la tension de l'une des sources d'entrée est supérieure à la tension minimum de démarrage. Lors du fonctionnement normal (après le démarrage), si la source actuellement sélectionnée (principale ou secondaire) se détériore et que sa condition devient moindre, l'appareil devrait commuter vers une source alternative, si cette source est de meilleure qualité.
5. Garantie Garantie limitée de 2 ans Le vendeur garantit que ce produit, s'il est utilisé conformément à toutes les instructions applicables, est exempt de tout défaut de matériaux et de fabrication pour une période de deux (2) ans à partir de la date d'achat initiale. Si le produit s'avère défectueux en raison d'un vice de matériau ou de fabrication au cours de cette période, le vendeur s'engage à...