Weather dependent precautions

Select a place where the rain can be avoided as much as
possible.
Be sure that the air inlet of the unit is not positioned towards the
main wind direction. Frontal wind will disturb the operation of the
unit. If necessary, use a screen to block the wind.
Ensure that water cannot cause any damage to the location by
adding water drains to the foundation and prevent water traps in
the construction.
Do not install the unit in areas where the air contains high levels
of salt such as that near the ocean.

Selecting a location in cold climates

NOTICE
When operating the unit in a low outdoor ambient
temperature, be sure to follow the instructions described
below.
To prevent exposure to wind and snow, install a baffle plate on
the air side of the outdoor unit:
1 Baffle plate
REYAQ10~16P7Y1B
VRVIII system outdoor unit
4PW62582-1A – 08.2011
In heavy snowfall areas it is very important to select an
installation site where the snow will not affect the unit. If lateral
snowfall is possible, make sure that the heat exchanger coil is
not affected by the snow (if necessary construct a lateral
canopy).
7.
D
IMENSIONS AND SERVICE SPACE

7.1. Dimensions of outdoor unit

1
129 160
1 Construct a large canopy.
2 Construct a pedestal.
Install the unit high enough from the ground to prevent
burying in snow.
A
1162
B
1032
1109
1300
(distances shown are in mm)
1
2
B
64
67
67
765
Installation manual
8