Wiring
• Mount in 2-gang U.S. wallbox 3.5 in. (89 mm)
deep or 4 x 4 in. (102 mm) junction box 2.1 in.
deep (53 mm). Indoors only.
• This device generates heat; mount only where
ambient temperature is 32 - 104 °F (0 - 40 °C).
• Mount with arrows facing up to ensure adequate
cooling.
• Allow 4.5 in. (114 mm) above and below unit and
between faceplates when mounting several in a
vertical layout.
• Mount so line (mains) voltage wiring is at least
6 ft. (1.8 m) from sound or electronic equipment
and wiring.
• Mount within 7° of true vertical.
Dimensions
All Modules: Front View
6.3 in.
(160 mm)
4
GRAFIK Eye
Power Modules
®
5.1 in.
(129.5 mm)
• Provide #12 AWG (2.5 mm
(75 °C minimum) for input power and load
circuit.
• Strip 1/2 in. (12 mm) insulation from wires
before connecting.
• Run separate neutral for load circuit - no
common neutrals.
Note! Plastic faceplate must be installed on
module for normal operation (all models).
Switching and
3-Wire Fluorescent Modules:
Side View
Phase-Adaptive Module:
Side View
2
) copper (Cu) wires
1.2 in. (30.5 mm)
0.4 in. (10 mm)
1.2 in. (30.5 mm)
1.2 in. (30.5 mm)
R