Trigger And Digital Inputs; Digital Outputs - Siemens SISTORE MX Manual De Instalación

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

7.2.1

Trigger and digital inputs

7.2.2

Digital outputs

Siemens Building Technologies
Fire Safety & Security Products
All manuals and user guides at all-guides.com
The HVR is equipped with optocouplers that enable the connection of floating
contacts. The contacts will be triggered when the inputs are shorted.
The switching voltage of the switches is 5 V ±10 %, with a max. switching current
of 5 mA. The inputs are provided with suppression circuits to prevent damage to
the device when voltages up to 24 V are applied.
There are 16 trigger inputs and 4 digital inputs available. These trigger inputs are
edge triggered. The trigger edge which is to initiate a trigger event can be selected
with the software (SISTORE RemoteView and SISTORE MX).
Input circuitry of the optocoupler
R
V
+
1K2
Digital In
_
Fig. 8
Optocoupler – input circuitry (example of pin assignment)
The 4 digital inputs can be used to control external events.
The outputs ground a connected consumer. All outputs can handle a maximum
current of 50 mA. Fusing of the outputs is implemented with reversible fuses. All
outputs are short circuit proof.
If inductive consumers are connected, we recommend using appropriate protective circuits.
U1
Optokoppler
D1
Fig. 9
Optocoupler – output circuitry (example of pin assignment)
Description of SISTORE MX 3G / MX 3G DVD
UB
Optokoppler
F1
50 mA
5 - 24 V
Digital Out
23
02.2009

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Sistore mx dvdSistema mx 3gSistema mx 3g dvd

Tabla de contenido