Operating conditions
•
The mains voltage must lie within the specified range; see
A deviation of ± 10 % is permissible.
•
The rated frequency must be within ± 3 Hz of the value specified.
•
The ambient temperature must be below 55 °C. For further options, see
Technical data.
The cooling unit must only be used in such a manner as to ensure that the specified cooling capacity is able to
meet actual demands.
Only the specified coolant may be used.
NOTE
Spare parts from third-party manufacturers can damage the unit
Internal temperatures below the dewpoint or damaged switch cabinet seals cause excessive accumulation of
condensate.
Only use specially harmonized manufacturer parts for safe and reliable operation.
For Pfannenberg spare part numbers, see Spare part orders.
4.5
Service interface
•
The service interface (1) can be used to change operating parameters.
•
For this purpose, a USB adapter (2) and the ECoolPLANT 2.X configuration software and USB driver software
are required.
•
The connection for the USB adapter is marked on the electrical circuit diagram with the identifier X28.
•
The USB adapter enables connection to a computer that works with the ECoolPLANT 2.X configuration
software. The detailed use is described in the corresponding operating manual for the ECoolPLANT 2.X
software.
•
Remove the USB adapter (2) from the unit after use. The service interface (1) is only provided for temporary
data exchange in order to read system notifications, etc. Continuous operation is prohibited.
The USB adapter is available as an accessory, see
The ECoolPLANT software (3) is available for download free of charge on the website:
https://www.pfannenberg.com/
The corresponding operating manual for the ECoolPLANT software is available
Pfannenberg.
Operating Manual DTS and DTI 6X1E Premium Controller X-Series (XC) 086100018 © Pfannenberg GmbH