Descargar Imprimir esta página

Leuze electronic CSL 505 Instrucciones Para La Instalación Y El Uso página 2

Cortina óptica de conmutación
Ocultar thumbs Ver también para CSL 505:

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

Installation and operating instructions
Switching light curtain CSL 505
Function
The CSL 505 switching light curtain monitors a defined control area with multiple
invisible infrared light beams. The light curtain systems consist of a transmitter
bar (Tx) and a receiver bar (Rx) made of anodized aluminum. They operate on
the principle of multiple throughbeam photoelectric sensors, whose output
signals are linked. If any light beam between transmitter and receiver is
interrupted, this is registered by the integrated evaluation electronics and
signaled at the antivalent push-pull signal outputs (PNP & NPN).
Intended use
The CSL 505 switching light curtain can be mounted on building
components, machine elements as well as other support elements. The
device must be secured with the existing fastening options (holes, bolts, ...).
Declaration of Conformity
The product satisfies the following standards:
EU Directive
2004/108/EC
Interference emission EN 55022:2010
Interference rejection EN 55024:2010
Degree of protection
EN 60529
Proximity switch
EN 60947-5-2
cCSAus
UL 61010-1 (Third Edition):2012-05;
CAN/CSA-C22.2 No. 61010-1-1
Leuze electronic GmbH + Co KG in D-73277 Owen, possesses a certified
quality assurance system in accordance with ISO 9001.
Safety notices
Please observe the safety notices of the original operating instructions.
Mounting
CSL 505 switching light curtains can be mounted on building components,
DIN rails as well as other support elements.
Technical data
Housing
Aluminum, clear anodized, dark-red plastic film
Connection
4-pin M8 connector or open cable end
Cables (optional)
4-pin cable with M8 socket available in various lengths as
accessory
24 V DC (18...30 V DC) with max. 10% ripple
Operating voltage
(DC voltage)
Nominal: 3.1 W, peak: 6.5 W (2 MHz, 100 s)
Power consumption
7.5 A (max), 40 s
Switch-on current
Outputs
Short-circuit proof, max. 150 mA
Environmental data
-30 °C to +50 °C, air humidity < 90 %, non-condens.
Operating range
300 mm up to 5,000 mm
Response time
Cycle time approx. 1 ms/beam plus basic time
(approx. 4 ms)
Max. number of
160 logical beams
beams
Grid:
5 / 12.5 / 25 / 50 / 100 mm
Degree of
IP 65
protection
Elevation
< 2000 m
Degree of
2
contamination
© Leuze electronic GmbH + Co. KG, In der Braike 1, 73277 Owen, Germany, Phone: +49 (0) 7021/573-0, Fax: -199, info@leuze.de, www.leuze.com We reserve the right to make changes 2018/03 Art. no. 50130104-02
Installation recommendations
1
Teach event
The teach event is important for ensuring the function of the light curtain.
Therefore, perform the teach event on the receiver after every change to
the bars. For an error-free teach event, the monitoring range must be clear
and both LEDs of the receiver bar must illuminate continuously. If the teach
event was not successful, please check the alignment of the transmitter and
receiver
When switching on, connect pin 2 or
pin 4 of the receiver bar to +24 V DC.
Both LEDs on the receiver bar
illuminate. The first valid value is
stored.
Completely disconnect the voltage of
the light curtain. Also disconnect the
voltage on pin 2 / pin 4 prior to the
next restart.
Check the switching function.
2
1
except for -ER model
2
approx. 1000 ... 10000 mm for -ER model
Read these instructions before commissioning.
Mount the bars without any mechanical loading.
In general, rough alignment of the bars is sufficient.
The transmitter bar and receiver bar must be able to "see"
over the entire monitoring range.
For optical synchronization of transmitter and receiver, either
the bottom or top beam (configurable) is used. This beam
must not be continuously interrupted or suppressed.
Only connect and disconnect bars while in a de-energized
state.
A potential difference of 60 V between the bar housing and
the supply voltage must not be exceeded.
Avoid ground loops: all bars must have the same grounding
potential.
Interference from ambient light (e.g., from flash lamps or
sunlight) on the receiver bar is to be avoided.
Avoid object reflections.
Mutual interference of optical sensors is to be avoided.
 Teach event starts
 Teach ok
 Sensitivity data is stored
 Teach event concluded
M8 connection diagram
+24 V DC
1
bn
2 *
4
M8 terminal plug, front
n.c.
2
wh
TX
view
1
3
GND
3
bu
TX_Off
4
bk
M8
Pin
TX
male
/ female
1, 3
+24 V DC, GND
+24 V DC
1
bn
2*
n.c.
Q1_RX
*
2
wh
RX
GND
4
TX_Off
3
bu
Q2_RX
4
bk
* is used during the teach event
1)
see original operating instructions
Function assignment
By reversing the polarity of the supply voltages on the transmitter and
receiver, it is possible to switch between predefined device functions:
Pin 1
Pin 3
Description
Extended operating range: 1.0 ... 5.0 m
+24 V DC
GND
Reduced operating range: 0.3 ... 1.3 m
GND
+24 V DC
Pin 1
Pin 3
Description
+24 V DC
GND
Only parallel beams
GND
+24 V DC
Parallel and diagonal beams
The depicted assignments are standard settings. The assigned functions
can be freely configured. For configurations that differ from the standard
configuration, please observe references to a configuration provided with
the product or the technical information.
Status LED
LEDs on the transmitter and receiver are used for diagnostics.
Receiver
Transmitter
LED1
LED2
Status
Not ready
Ready, interrupted
beam
Ready
Error
Error, interrupted beam
Configuration error
Serious error*
RX
Dark switching *
1)
Light switching
LED
Status
Not ready
Ready
Error
* during the teach event

Publicidad

loading