[33]
# Configuración de las señales digitales
[34]
# Numero de ISCs
[35]
108,
[36]
# señal digital,alarma,filtra act.,filtra desact.,flanco alarma
[37]
0,0,0,0,0,0,
[38]
1,0,0,1,0,0,
[39]
2,0,0,1,0,0,
[40]
...
[41]
107,1,0,1,0,1,
[42]
# ISE
[43]
17,
[44]
# mando,isc estado(equipo,nº señal),tiempo,negada,isc ok(equipo,nº señal),isc
[45]
#fallo(equipo,nº señal),doble,nº bloqueos,(equipo,señal dig) por bloqueo
[46]
0,1,36,10000,0,1,36,1,78,0,2,1,71,0,256,15,0,
[47]
1,1,37,10000,0,1,37,1,78,0,2,1,71,0,256,15,0,
[48]
2,1,39,10000,0,1,39,1,-1,0,2,1,72,0,256,15,0,
[49]
...
[50]
16,1,1,10000,0,1,1,1,-1,0,0,
[51]
# ISS
[52]
0,
[53]
# ISS,Dir,Isc,time,neg,Analog ?
[54]
# MEA
[55]
8,
[56]
# MEA * Factor de Conversion =
[57]
# a,b donde a=(max-min)/4095 y b=min
[58]
0.46886447,0,
[59]
0.46886447,0,
[60]
0.46886447,0,
[61]
...
[62]
0.03516484,0,
[63]
# CON
[64]
0,
[65]
# CONT * FACTOR de Conversion =
[66]
# a,b donde a=(max-min)/4095 y b=min
[67]
#
[68]
#========================================================================
[69]
# EQUIPO LOGICO Nº 2 (SPAC-538C RELE DIRECCIONAL LINEA PITUAÇU 69kV 02J6)
[70]
#========================================================================
[71]
# Dir. PROCOME del equipo lógico Procome asociado a un Equipo completo SPA de
[72]
# ABB,
[73]
# TimeOut RX (ms), Nº ISCs, ISC Máx, Nº ISEs, ISE Máx, Nº ISSs, ISS Máx,
[74]
# Nº MEAs, Nº CONs, ISC Local,
[75]
2,500,31,30,0,0,0,0,0,0,0,
[76]
# Nº de módulos (Control y/o Protección) que componen el Equipo SPA de ABB,
[77]
3,
[78]
# Identificación Módulo SPA, Dir. física Módulo SPA,
[79]
SPCS4D1F,111,
[80]
SPCS3C4,112,
[81]
SPCS4D1F,130,
[82]
...
© ZIV Aplicaciones y Tecnología, S. A. Zamudio, 2004
configuración de los emuladores de protocolo
Valor Real
VALOR REAL
// PROTECCIÓN SOBREINTENSIDAD DIRECCIONAL BIFÁSICA SPCS 4D11
// PROTECCIÓN SOBREINTENSIDAD DIRECCIONAL DE NEUTRO SPCS 3C4
// PROTECCIÓN SOBREINTENSIDAD DIRECCIONAL BIFÁSICA SPCS 4D12
B.14-5
LCPX403A