SETTING OF THE DIP-SWITCHES
Factory setting
All the module DIP switches are at pos. 0 as default configuration. This set corresponds
to the following default configuration :
Thermocouple Type :
Line Rejection :
Input Filter :
Measurement Range :
Output Signal :
Output Signal in case of
fault :
Over-Range :
Auxiliary Output
Threshold :
It is understood that this configuration is valid only with all the DIP switches at position
0. If also one Dip is moved, it is necessary to set all the other parameter as indicated
on the following tables.
Note: for all following tables
The indication
No indication is provided when the DIP-switch is set in Position 0 (OFF).
THERMOCOUPLE TYPE
SW1
1
2 3
J
K
R
S
T
B
E
N
(*) The input filter stabilizes the measurement and guarantees the repeating of the
disturbance signal overlapping the measurement signal but slows down the response
time. If the maximum response speed is not required, it is advisable to insert it.
MEASUREMENT RANGE START
J Type
SW1
6
7 8
Default *
0 °C
100 °C
200 °C
300 °C
500 °C
-100 °C
-200 °C
* If all the dip-switches are set to OFF position, the default configuration is valid;
otherwise the value of this parameter is 0 °C, as for the other thermocouple types.
J
50 Hz
Present
0...1000 °C
4..20 mA
Towards the top of the output range
YES: a 2.5% over-range value is acceptable;
a 5% over-range value is considered a malfunction.
0% of the nominal scale
indicates that the DIP-switch is set in Position 1 (ON).
K Type
R Type S Type
0 °C
100 °C
100 °C
200 °C
200 °C
400 °C
300 °C
400 °C
600 °C
800 °C
600 °C
-100 °C
800 °C
-200 °C
1000 °C
LINE REJECTION
SW1
INPUT FILTER (*)
SW1
0 °C
0 °C
100 °C
200 °C
300 °C
400 °C
-150 °C
600 °C
-100 °C
800 °C
-200 °C
1000 °C
MI00111 -E
3
4
60 Hz
50 Hz
5
Present
Absent
T Type B Type E Type N Type
0 °C
0 °C
400 °C
400 °C
50 °C
500 °C
100 °C
600 °C
200 °C
-50 °C
800 °C
1000 °C
1200 °C
1400 °C
ENGLISH - 5/8
0 °C
0 °C
100 °C
100 °C
100 °C
200 °C
200 °C
300 °C
300 °C
500 °C
400 °C
700 °C
500 °C
-100 °C
-100 °C
-200 °C
-200 °C