Installation Conditions - Eco MODINE EGK Serie Manual Tecnico

Condensadores de aire y refrigeradores de líquido con motores axiales
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

6. Installation conditions

6.1
The model described in this manual is a component of a refrigeration system and must only be installed by
authorised personnel.
6.2
The model is fitted with axial fans that are not suitable to withstand additional static pressures and therefore it
cannot be channelled, air intake filters cannot be installed and in the area dedicated to installation there must
be no strong currents of air which are contrary to the flow of the motor fans.
6.3
Installation must be carried out preferably outside. Where the model is to be installed inside, it is essential to
provide an air intake that excludes any additional static pressure.
6.4
The base must be appropriate to the weight of the model when operational (see the drawing supplied with the
model).
6.5
The equipment must be securely anchored to the support base in order to prevent the transmission of noise.
Possibly use shock absorbers.