Carrier 50CO Instrucciones De Instalación, Funcionamiento Y Mantenimiento página 53

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

11 - TECHNICAL SPECIFICATIONS
Connection:
it is supplied with a flexible water supply tube at the back of the unit.
To drain it, carry out siphoning.
Warning: the water temperature can reach 100°C.
11.2.4 - Condensate drain pump:
This option is only available if the humidifier option has not been requested.
Characteristics:
- Power supply: 230V-50Hz-90W
- Max. flow rate: 500 l/h
- Max. discharge height: 5.4 m
- Built-in check valve
Table of actual flow rates for pump SI 1805
The pressure drops defined in this table are
calculated using a 10 mm diameter flexible
connection
Connect a flexible connection with an int. Ø 10 mm (3/8") (not supplied by CARRIER) to the pump discharge.
For OVER models (3 and 5), if using a spreader beam and slings, the PVC tube will not be directly connected to the pump, for handling
reasons. It must therefore be angled in the right direction and fixed to the clamp, as shown below.
Condensate discharge
with check valve
Discharge
height
1 m
2 m
3 m
4 m
5 m
Total pipe length
5 m (l/h)
10 m (l/h)
460
380
390
320
300
250
200
180
90
80
20 m (l/h)
30 m (l/h)
280
200
240
180
190
150
130
100
60
50
53