10. Display Error codes

If an error occurs, the error code is displayed in the main loop. All windows, however, can still be accessed by pressing
the button. If the button is not pressed for approx. 4 min, the error code is automatically displayed again. The error mes-
sage disappears automatically as soon as the source of the error is corrected. All errors that exist for longer than 6 min,
are saved in the error memory.
Error code
Description
C - 1
Basic parameter error in flash or RAM - Meter must be replaced
E 1
Temperature range outside [-19.9 °C...199.9 °C] e.g. sensor short-circuit, sensor break
E 3**
Forward and return sensor reversed
E 4
Hardware error US measurement, e.g. transducer or control defective or short circuit
E 5
Communication not possible (too frequent read-out)
E 6**
Flow direction of flow meter incorrect
E 7
No plausible ultrasound receiver signal, e.g. air in the measuring path
E 8
No primary power supply (only with power supply unit); supply via backup battery
E 9
Battery nearly discharged, design lifetime reached
E A*
Leak: Pipe break detection
E b*
Leak: Energy meter leak detection
E C*
Leak: Leak pulse input 1
E d*
Leak: Leak pulse input 2
* optional ** application dependent