EXPLOSION HAZARD—Substitution of components may impair suitability
for Class I, Division 2.
Keep tightly closed when in operation.
The Model 191XL LED Beacon is a UL listed visual signal for operation in harsh
environments and hazardous locations, and has been investigated by UL as meeting
Type 4X and IP66 enclosure requirements. The unit is rated for operation on 100–265
VAC, 50/60Hz, 0.21A, 277VAC, 50/60Hz, 0.13A, or 24VDC/AC 50/60Hz, 0.38A. The
191XL can be supplied with colors of red, amber, green, blue, and clear. The 191XL
is factory set to operate 60 flashes/minute. There is an option to operate the LED in
steady on mode. Refer to Section III A. for details.
These devices are intended for permanent installation and operation in accordance
with Title 46, Code of Federal Regulations, Parts 110–113, or Title 33, Code of Federal
Regulations, Part 183, Sub-part I, Section 183.410, and the applicable requirements of
the American Boat and Yacht Council, Inc., and/or ANSI/NFPA 302, "Fire Protection
Standard for Pleasure and Commercial Motor Craft."
II.
INSTALLATION
A.
Unpacking
Damaged globes can lead to explosions that could result in serious injury or
death.
After unpacking the Model 191XL, examine it for damage that may have
occurred in transit. If the equipment has been damaged, do not attempt to install or
operate the unit. File a claim immediately with the carrier, stating the extent of the
damage. Carefully check all envelopes, shipping labels and tags before removing or
discarding them. Disposal of all shipping materials must be carried out in accordance
with national and local codes and standards.
B.
Mounting
To reduce the risk of fire or explosion, do not install in a hazardous location
if the operating temperature exceeds the hazardous atmosphere's ignition
temperature. Before proceeding, consult the product nameplate and determine
the unit's operating temperature.
To comply with NEC Section 300-14, which requires a minimum of 6 inches of
free conductor at a junction, when mounting the Model 191XL, the mounting
pipe used to join the unit to a splice box should be no longer than 10 inches.
NOTE
-2-