Descargar Imprimir esta página

Siemens SITOP power 20 Manual De Instrucciones página 4

Ocultar thumbs Ver también para SITOP power 20:

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

WARNING
!
Hazardous voltages are present in certain parts of this electrical equipment during operation. Incorrect handling of the
equipment can result in death, severe personal injury or substantial property damage. Only qualified personnel are allowed
to work on or around this equipment. The successful and safe operation of this equipment is dependent on proper transport,
storage and installation.
The mains switch has to be switched off and prevented from being switched on again before installation or maintenance. If
these rules are not adhered to, contact with live parts or improper use can result in death or severe personal injury
Potentiometer R230 is only allowed to be actuated using an insulated screwdriver to DIN 7437, because accidental contact
may be made with parts inside the equipment carrying dangerous electrical voltage.
CAUTION
The device may only be opened by qualified personnel.
Electrostatically sensitive devices (ESD)
Description and Design
The SITOP 24V/ 20A power supply is a device of the built-in type. The pertinent DIN/VDE standards or country-specific specifications apply
to the installation of the device.
Power supplies with primary AC input for connection to 120 or 230V, 50/60 Hz single-phase AC system. Output voltage +24V DC,
potentialfree, protected against short-circuit and open-circuit conditions.
Technical Data
Input values
Rated input voltage:
120/230V, 50/60Hz
Operating voltage range:
93 to 132V / 187 to 264V
Efficiency at full load (typical):
87%
Inrush current limitation (25°C) as standard
2
<81A, <8A
s
Recommended miniature circuit-breaker
characteristic C
16A
Input current at 120/230V:
8.0/3.3A
rms
Power input (active power):
552W
Installation
Mounting on standard rails as per DIN EN 50022-35x15/7.5.To ensure adequate cooling, the device must be installed vertically so that the
input terminals are at the top and the output terminals at the bottom. Be sure to leave a minimum clearance of 50 mm above and below
and 40mm to the left of the device.
The supply voltage (AC 120/230V) and necessary jumper for the 120V range must be connected in accordance with VDE 0100 and VDE
0160. A protective device (fuse) and an isolating device for disconnecting the power supply must be provided. If the equipment is operated
in the 120V range, a jumper must be wired between the two "AC120V-JUMPER" terminals. It must have the same cross-section and
insulation as the power supply cables. It must not be longer than 100mm ( 4in.).
!
WARNING: The necessary jumper for operating voltage range 93-132V also carries dangerous electrical voltage!
Connections and terminal assignment
Terminals
Function
L1, N
Input voltage AC 120/230 V
PE
Protective earth conductor
AC 120V-
Necessary jumper for operating voltage
JUMPER
range 93-132V
L+, M
Output voltage DC 24 V
SIEMENS AG ÖSTERREICH, 09.2001
Output values
Output DC voltage:
As supplied: 24V ±1%
Setting range by screwdriver adjustment of
potentiometer R230 (beneath device, position
shown on page 2) from 22.8 to 26.4V
Output voltage ripple:
<150mV
residual ripple
peak-to-peak
<240mV
switching peaks
peak-to-peak
Output DC current:
0 to 20A
It is permissible to connect two devices of the same
type in parallel in order to increase the output.
(See notes in Catalog KT 10)
Environment
Temperature
Storage and transport: -25 to +85°C
Operation:
0 to +55°C
Operation in parallel connection or at increased
output voltage: 0 to +45°C
Humidity rating: corresponding to Climatic Category
3K3 as per EN60721, Part 3
No condensation, natural air cooling
Pollution degree 2
Terminal range
Remarks
2
0.14 to 2.5mm
Screw-type terminals. Use a screwdriver with a blade width of
(AWG 22..12)
3.5 mm. Recommended tightening torque 0.5-0.7 Nm
2
0.33 to 10 mm
Screw-type terminals. Use a screw driver with a blade width of
(AWG 22...8)
5 mm. Recommended tightening torque 1.2 Nm.
4/8
Protection and monitoring
function
Steady-state current limitation: typ. 22A
Short-circuit behaviour (output)
automatic restart
Power system failure buffering:
>10ms at 93/187V
Standards and specifications
Degree of protection: IP20 to IEC 529
Class of protection: 1 to IEC 536
Safety to VDE 0160 and VDE 0805 (EN60950):
SELV
Emitted interference to EN50081-1
Radio interference suppression to EN55022, limit
value characteristic B
Noise immunity to EN 50082-2 incl. Table A4
Limitation of input current harmonics to
EN61000-3-2
UL508/CSA 22.2 FILE E143289
Weight
2 kg
English
SITOP power 20

Publicidad

loading

Este manual también es adecuado para:

6ep1336-2ba