Accessory Installation And Operation - WEG MMF-03-SP Guía De Instalación, Configuración Y Operación

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

MMF-03-SP Memory Module
4 ACCESSORY INSTALLATION AND
OPERATION
The MMF-03-SP-x Memory Module is easily connected
to the CFW11 frequency inverter. The procedures below
must be observed for proper operation:
Step 1: disconnect the general power supply of the
CFW11 frequency inverter and remove the MMF-03
accessory from the CFW11.
Step 2: connect the MMF-03-SP-x and energize the
CFW11 frequency inverter.
Step 3: follow the sequence of parameters below to
update the CFW11 firmware:
P0000 = 5 (Allow changing parameters).
P0200 = 0 (Disable the password).
P0000 = 248 (Allow parameter P0600 to be viewed).
P0600 = 2 (Save the VE5.31 special firmware on the
CFW11).
Step 4: wait for the saving of the firmware. During this
procedure, the inverter cannot be de-energized.
Step 5: check if the firmware version has been recorded
successfully, ie, if P0023 = 5.31.
Step 6: follow the sequence of parameters below to
enable the Pump Genius Multiplex application to run:
P0000 = 5 (Allow changing parameters).
P1001 = 1 (Run Application).
Step 7: check if the Pump Genius Multiplex application
is running, ie, if P1000 = 4 (running application).
Step 8: check if the version of the Pump Genius Multiplex
application is the same as being informed on the label on
the front of the accessory, ie, if P1010 = 2.1x.
Step 9: using the WLP 9.9x tool or above, create a new
project as described in chapter 4 of the Pump Genius
Multiplex application manual.
Step 10 : configure the Pump Genius Multiplex
6 | CFW11

Publicidad

Tabla de contenido
loading

Tabla de contenido