Application area, use in gas and dust atmospheres (zones and
divisions)
Associated apparatus for non-hazardous locations
The controllers VEGAMET 841, 842, 861, 862 may be installed and operated outside of hazardous
areas as associated equipment.
5
Special operating conditions
The following overview is listing all special properties of VEGAMET 841, 842, 861, 862, which make
a labelling with the symbol "X" behind the certificate number necessary.
Ambient temperature
You can find the details in chapter " Thermal data" of these safety instructions.
Electrostatic charging (ESD)
You can find the details in chapter " Electrostatic charging (ESD)" of these safety instructions.
Zone 2 applications
The device must be installed in a protective housing or a switching cabinet with IP54 according to
IEC 60079-0.
The device may only be used in an area with a minimum pollution level of 2 or better, as defined in
IEC 60664-1.
6
Safe operating mode
General operating conditions
Do not operate the instrument outside the electrical, thermal and mechanical specifications of
the manufacturer
Connection conditions
The connection cable of VEGAMET 841, 842, 861, 862 has to be wired fix and in such a way
that damages can be excluded
If the temperature at the inlet components exceeds 60 °C (USA and Canada), temperature-
resistant connection cables must be used
7
Important information for mounting and maintenance
General instructions
The following requirements must be fulfilled for mounting, electrical installation, setup and mainte-
nance of the instrument:
The staff must be qualified according the respective tasks
The staff must be trained in explosion protection
The staff must be familiar with the respectively valid regulations, e.g. planning and installation
acc. to ANSI/ISA RP12.06.01 „Installation of Intrinsically Safe Systems for Hazardous (Classi-
fies) Locations" and the National Electrical Code
Make sure when working on the instrument (mounting, installation, maintenance) that there is no
explosive atmosphere present, the supply circuits should be voltage-free, if possible.
The instrument has to be mounted according to the manufacturer specifications, the Certificate
of Conformity and the valid regulations and standards
Modifications on the instrument can influence the explosion protection and hence the safety,
therefore repairs are not permitted to be conducted by the end user
Modifications must only be carried out by employees authorized by VEGA company
4
(ANSI/NFPA 70) or Canadian Electrical Code
®
c-UL-us
VEGAMET 841, 842, 861, 862