Operation - Protemp PT-45-KFA Manual Del Usuario

Ocultar thumbs Ver también para PT-45-KFA:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Fueling The Heater:
Kerosene (K-1)
For optimal performance of this heater, it is strongly
suggested that K-1 kerosene be used, especially in
temperatures lower than 26°F (-3°C). K-1 kerosene
has been refined to virtually eliminate contaminants,
such as sulfur, which can cause a rotten egg odor
during the operation of the heater. Using diesel fuel
can cause excess soot production. Do not use Bio-
Diesel as this fuel will damage your heater's seals and
filter.
- CSA certified for use with K-1 kerosene, no. 1 & no.
2 diesel, JP8/Jet A Fuel, no. 1 and no. 2 fuel oil.
DO NOT use any fuel that is not approved above.
DANGER
FIRE OR EXPLOSION COULD RESULT.
CAUTION
FILL THE TANK OUTDOORS. BE SURE THAT THE
HEATER IS ON LEVEL GROUND WHEN FUELING,
AND NEVER OVERFILL THE TANK.
WARNING
- NEVER use fuel such as, benzene, alcohol, white
gas, camp stove fuel, paint thinners, or other oil
compounds in this heater. THESE ARE VOLATILE
FUELS THAT CAN CAUSE A FIRE OR EXPLOSION.
- NEVER store kerosene in the living space. Kerosene
should be stored in a well ventilated area outside
the living area.
- NEVER store kerosene in direct sunlight or near a
source of heat.
- NEVER use kerosene that has been stored from one
season to the next. Kerosene deteriorates over time.
OLD KEROSENE WILL NOT BURN PROPERLY IN
THIS HEATER.
NOTE: Kerosene should only be stored in a blue
container that is clearly marked "Kerosene." Never
store kerosene in a red container. Red is associated
with gasoline.
© 2019 Pinnacle Climate Technologies, Inc.
NEVER LEAVE HEATER UNATTENDED WHILE BURNING OR WHILE
®

OPERATION

NEVER REFUEL THIS
HEATER WHILE IT IS
HOT OR OPERATING.
NEVER FILL THE
FUEL TANK IN-
DOORS. ALWAYS
DO NOT USE GASO-
LINE OR CRANKCASE
DRAININGS.
CONNECTED TO A POWER SOURCE
Ventilation:
- Risk of indoor air pollution and Carbon Monoxide
Poisoning. Use heater only in well ventilated
areas.
- Refer to Safety Information on page 3 for
information about Carbon Monoxide Poisoning.
DANGER
- ALWAYS provide a fresh air opening in the heated
space of at least three square feet (2,800 sq. cm)
for each 100,000 Btu / Hr. (29 kW) of heater
output. Provide a larger opening if more heaters are
being used.
Minimum Ventilation Opening Needed
45-KFA
1.4 ft.²
1250 cm²
Minimum Ventilation Opening Needed
175T-KFA
5.3 ft.²
4930 cm²
6
Kerosene Forced Air Heater User's Manual
CARBON MONOXIDE
POISONING MAY LEAD TO
DEATH!
80T-KFA
140T-KFA
2.4 ft.²
4.2 ft.²
2230 cm²
3902 cm²
215T-KFA
6.5 ft.²
5990 cm²

Publicidad

Capítulos

Tabla de contenido
loading

Este manual también es adecuado para:

Pt-80t-kfaPt-140t-kfaPt-175t-kfaPt-215t-kfa

Tabla de contenido