Configuration - Festo CPV Serie Instrucciones Para El Usuario

Ocultar thumbs Ver también para CPV Serie:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 23
3

Configuration

Caution
The CPV Direct contains electronically sensitive compo-
nents. The CPV Ddirect will be damaged if you touch
the contact surfaces of the plug connectors and if you
do not observe the regulations for handling electro-
statically sensitive components.
Proceed as follows when configuring:
1. Switch off the power supply.
2. Remove the switch module.
3. Set the following with the DIL switches: baud rate,
extension to the CP system, station number.
4. Refit the switch module.
5. If the CP system is the first or last slave in a field bus
segment, a terminating resistor must be fitted
between the field bus cables (120
Warning
S Make sure that switch-on test pulses are sup-
pressed/switched off when you operate the CPV
Direct via a "safety I/O module".
S Check the measures required for putting your system
into a safe status in the event of an EMERGENCY
STOP.
Further information can be found in manual
P.BE-CP-CO2-.. .
Festo CPV..-GE-CO2-8 0107NH English
9
, 0.25 W).
17

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Cpv ge-co2-8Cvp serieCvp ge-co2-8

Tabla de contenido