I Combination of Y branch/header method
Example : 5 Indoor Units connected
: Outdoor Unit
: 1st branch (Y branch)
: Y branch
: Indoor Unit
: Header
: Sealed piping
➲ Refrigerant pipe diameter from branch to branch (B,C)
Downward Indoor Unit total capacity
[kW(Btu/h)]
≤5.6(19,100)
<16(54,600)
<22.4(76,400)
➲ Total pipe length = A+B+C+a+b+c+d+e ≤ 300m(984ft)
Longest pipe length
L
A+B+b ≤ 150m(492ft)
Longest pipe length after 1st branch
l
B+b ≤ 40m(131ft)
Difference in height(Outdoor Unit ↔ Indoor Unit)
H
H ≤ 50m(164ft) (40m(131ft) : Outdoor Unit is lower than Indoor Units)**
Difference in height (Indoor Unit ↔ Indoor Unit)
h
h ≤ 15m(49ft)
• * : Assume equivalent pipe length of Y branch to be0.5m(1.6ft), that of header to be 1m(3.3ft), calculation purpose
• ** : Indoor Unit should be installed at lower position than the header
WARNING
It is recommended that difference of piping length for pipes connected to the Indoor Unit is
minimized. Performance difference between Indoor Units may occur.
Branch pipe can not be used after header
Liquid pipe
Gas pipe
[mm(inch)]
[mm(inch)]
Ø6.35(1/4)
Ø12.7(1/2)
Ø9.52(3/8)
Ø15.88(5/8)
Ø9.52(3/8)
Ø19.05(3/4)
* Equivalent pipe length
A+B+b ≤ 175m(574ft)
Refrigerant Piping
[Unit:m(ft)]
L150 (492)
40 (131)
Installation Manual 29