Posicionador Electroneumático TZIDC-120
para el FOUNDATION Fieldbus
6.3

FM / CSA

6.3.1

CSA Certification Record

Certificate:
Class 2258 04
Class I, Div 1, Groups A, B, C and D;
Class II, Div 1, Groups E, F, and G,
Class III, Div 1, Enclosure Type 4X:
Model TZIDC-120, P/N V18347-x042x2xx0x Intelligent
Positioner
Input rated
Intrinsically safe with entity parameters of:
Terminals 11 / 12
Terminals 85 / 86
Terminals 41 / 42
When installed per installation Drawing No 901265
Temperature Code
Max. Ambient
IMPORTANT (NOTE)
The "x" in P/N denotes minor mechanical
variations or optional features.
Local communication interface LKS shall not be
used in hazardous location.
Each pair of conductors of each intrinsic safety
circuit shall be shielded.
1649904 (LR 20312)
PROCESS CONTROL
EQUIPMENT – Intrinsically Safe,
Entity – For Hazardous Locations
32 V DC; max. 15 mA (powered by
a SELV Circuit)
V max = 24 V
I max = 250 mA
C
= 2.8 nF
i
L
= 7.2 uH
i
U max = 30 V
I max = 50 mA
C
= 3.8 nF
i
L
= 0 uH
i
U max = 16 V
I max = 20 mA
C
= 60 nF
i
L
= 100 uH
i
T4
85 Deg C
6.3.2
FM Approvals
TZIDC-120 Positioner, Model V18347-a042b2cd0e
IS/I,II,III/1/ABCDEFG/T6,T5,T4
Entity, FISCO
Entity and FISCO Parameters
Terminals Type
Groups Parameters
Vmax Imax
+11 / -12 Entity A-G
24 V
+11 / -12 FISCO A-G
17.5 V 360 mA 2.52 W 2.8 nF 7.2 uH
+11 / -12 FISCO C-G
17.5 V 380 mA 5.32 W 2.8 nF 7.2 uH
+51 / -52 Entity A-G
16 V
+41 / -42 Entity A-G
16 V
+85 / -86 Entity A-G
30 V
NNI/I/2/ABCD/T6,T5,T4 Ta = 40 °C, 55 °C, 85 °C
S/II,III/2/EFG//T6,T5,T4 Ta = 40 °C, 55 °C, 85 °C
Enclosure type 4x
a = Case/mounting – 1, 2, 5 or 6
b = Output/safe protection – 1, 2, 4 or 5
c = 0
d = Optional mechanical kit for digital position feedback – 0, 1 or 3
e = Design (varnish/coding) – 1 or E
Equipment Ratings:
TZIDC-120 Positioners
Intrinsically safe, Entity and FISCO, for Class I, II and III, Division 1,
Applicable Groups A, B, C, D, E, F, G; nonincendive for Class I,
Division 2,
Group E, F and G hazardous (classified) indoor and outdoor NEMA 4x
locations.
The following temperature code ratings were assigned for
the equipment and protection methods described above:
T6 in ambient temperatures of 40 °C
T5 in ambient temperatures of 55 °C
T4 in ambient temperatures of 85 °C
10/18-0.24-ES
Ta = 40 °C,
55 °C, 85 °C-901265
Pi
Ci
Li
250 mA 1.2 W
2.8 nF 7.2 uH
20 mA
-
60 nF 100 uH
20 mA
-
60 nF 100 uH
-
-
3.7 nF < 1 uH