Posicionador Electroneumático TZIDC-120
para el FOUNDATION Fieldbus
6.3
FM / CSA
6.3.1
CSA Certification Record
Certificate:
Class 2258 04
Class I, Div 1, Groups A, B, C and D;
Class II, Div 1, Groups E, F, and G,
Class III, Div 1, Enclosure Type 4X:
Model TZIDC-120, P/N V18347-x042x2xx0x Intelligent
Positioner
Input rated
Intrinsically safe with entity parameters of:
Terminals 11 / 12
Terminals 85 / 86
Terminals 41 / 42
When installed per installation Drawing No 901265
Temperature Code
Max. Ambient
IMPORTANT (NOTE)
•
The "x" in P/N denotes minor mechanical
variations or optional features.
•
Local communication interface LKS shall not be
used in hazardous location.
•
Each pair of conductors of each intrinsic safety
circuit shall be shielded.
1649904 (LR 20312)
PROCESS CONTROL
EQUIPMENT – Intrinsically Safe,
Entity – For Hazardous Locations
32 V DC; max. 15 mA (powered by
a SELV Circuit)
V max = 24 V
I max = 250 mA
C
= 2.8 nF
i
L
= 7.2 uH
i
U max = 30 V
I max = 50 mA
C
= 3.8 nF
i
L
= 0 uH
i
U max = 16 V
I max = 20 mA
C
= 60 nF
i
L
= 100 uH
i
T4
85 Deg C
6.3.2
FM Approvals
TZIDC-120 Positioner, Model V18347-a042b2cd0e
IS/I,II,III/1/ABCDEFG/T6,T5,T4
Entity, FISCO
Entity and FISCO Parameters
Terminals Type
Groups Parameters
Vmax Imax
+11 / -12 Entity A-G
24 V
+11 / -12 FISCO A-G
17.5 V 360 mA 2.52 W 2.8 nF 7.2 uH
+11 / -12 FISCO C-G
17.5 V 380 mA 5.32 W 2.8 nF 7.2 uH
+51 / -52 Entity A-G
16 V
+41 / -42 Entity A-G
16 V
+85 / -86 Entity A-G
30 V
NNI/I/2/ABCD/T6,T5,T4 Ta = 40 °C, 55 °C, 85 °C
S/II,III/2/EFG//T6,T5,T4 Ta = 40 °C, 55 °C, 85 °C
Enclosure type 4x
a = Case/mounting – 1, 2, 5 or 6
b = Output/safe protection – 1, 2, 4 or 5
c = 0
d = Optional mechanical kit for digital position feedback – 0, 1 or 3
e = Design (varnish/coding) – 1 or E
Equipment Ratings:
TZIDC-120 Positioners
Intrinsically safe, Entity and FISCO, for Class I, II and III, Division 1,
Applicable Groups A, B, C, D, E, F, G; nonincendive for Class I,
Division 2,
Group E, F and G hazardous (classified) indoor and outdoor NEMA 4x
locations.
The following temperature code ratings were assigned for
the equipment and protection methods described above:
T6 in ambient temperatures of 40 °C
T5 in ambient temperatures of 55 °C
T4 in ambient temperatures of 85 °C
10/18-0.24-ES
Ta = 40 °C,
55 °C, 85 °C-901265
Pi
Ci
Li
250 mA 1.2 W
2.8 nF 7.2 uH
20 mA
-
60 nF 100 uH
20 mA
-
60 nF 100 uH
-
-
3.7 nF < 1 uH
15