Separate Power Supplies For Light And Sounder; Figure 3 Wiring For Single Power Supply - Federal Signal AV1-LED Manual De Instalación Y Mantenimiento

Luz led audiovisual
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Installation and Maintenance Manual
5. Strip a maximum of 0.25 in (6.4 mm) of wire insulation from
the ends of the power leads.
6. See Figure 3. To connect the wires to the terminal block, insert
the stripped ends of the wires into the connector as far as
they can go, then tighten the clamping screw. The maximum
tightening torque is 4.5 in-lb (0.5 N • m).
7. Reassemble the Model AV1-LED, restore power, and test the
unit for proper operation.
LINE/+
NEUTRAL/−

Separate Power Supplies for Light and Sounder

In some applications it may be beneficial to control the light
independent of the sounder. If this is the case, separate power
supply wiring for each of the devices can be connected to the
terminal block. Required for the installation are supply wires of
the appropriate size (14 AWG [2.0 mm2] maximum thickness).
SHOCK HAZARD—Do not connect the light to the system
while the power is on. Failure to heed this warning may cause
serious injury or death.
To wire the light and sounder to separate power supplies:
1. Turn off power to the system.
2. Remove and retain the three #8 screws securing the upper
housing to the lower housing. Remove the upper housing.
3. Remove the factory field-wiring leads from the terminal block.
10

Figure 3 Wiring for single power supply

TERMINAL
BLOCK
Model AV1-LED Lights
RED
YELLOW
WHITE
PCBA
CONNECTOR
290A6506

Publicidad

Tabla de contenido
loading

Tabla de contenido