AT-8000
Tracing Energized Wires - Smart Sensor
Set-up:
1
Test Leads
AT-8000-T
Proper connection
with separate
ground
1. Plug the green and red test leads into the Transmitter.
2. Connect the green wire to a separate ground.
3. Connect the red test lead to the wire being
traced. For receptacles, make sure to connect the
test lead to the line (hot) wire. For Energized
systems the signal will ONLY be transmitted
between the load-side to which the Transmitter is
connected and the source of power.
Set-up:
2
Transmitter
Transmitter
indicator showing
signal in
HIGH mode
1. Turn on the Transmitter.
2. Verify that the test leads are properly connected;
the red LED voltage status light should be on for
circuits with voltage above 30 V AC/DC.
3. Select HIGH signal mode by pressing HI.
2
Amprobe
®
| info@amprobe.com | Fluke Corporation, Everett, WA 98203 | Tel: 877-AMPROBE (267-7623)
AT-8000-T
TRANSMITTER
Blinking
HI
LO
TM
Receiver:
Energized Smart Sensor
The Smart Sensor
TM
enables easier wire tracing by
showing the direction and position of the wire and is the
recommended method for tracing Energized wires.
ENERGIZED:
DE-ENERGIZED:
1. Turn on the Receiver and select SMART SENSOR
mode using the directional arrows.
2. Hold the Receiver with the Smart Sensor
the target area.
3. Move the Receiver in direction indicated by the
arrow on the screen. If the screen flashes a "?" in a
red target then either no signal is detected or the
signal is not adequate enough to display direction;
increase the sensitivity using the "+" button on the
Receiver.
4. Press ENTER when complete to return to the
home screen.
Receiver locked on wire
TIP: For best results, keep the Receiver at least 3
feet from the Transmitter and its test leads to
minimize signal interference and improve wire
tracing results. Select the "Long" Smart Sensor
Range in the Settings Menu if working with wires
that are greater than 3 feet deep.