MALFUNCTION CODE OF OUTDOOR UNIT

Table 4-1
No.
Communication error between main board and
1
compressor drive board
2
DC bus voltage error
3
Inverter-module protection
4
3 times of P2 protection in 30 minutes
5
Qty. of indoor units mismatching
6
High pressure sensor fault
M-HOME for the indoor and outdoor units does not match
7
8
Phase sequence error
9
Communication error between indoor and master unit
10
T3 & T4 temperature sensor error
Abnormal power supply voltage
11
12
DC fan motor error
13
Discharge temperature sensor error
14
TL sensor error
15
E6 protection appears 6 times in 1 hour
16
Inverter module Temp. protection
17
High pressure protection
18
Low pressure protection
19
Compressor current protection
20
Discharge Temp. protection
21
High Temp. protection of condenser
22
Typhoon protection
23
Inverter compressor module error
24
DC bus low voltage protection
25
DC bus high voltage protection
26
MCE error
27
Zero speed protection
28
Phase sequence protection
Compressor frequency variation greater than 15Hz
29
within one second protection
Actual compressor frequency differs from target
30
frequency by more than 15Hz protection
31
PED protection board error
32
High pressure switch protection on driver board
Display Function Instruction
1. When stand by, LED displaying the amount of indoor units online which communicate with outdoor units.
2. When operation, LED displaying frequency value of compressor.
3. When defrost, LED displaying "dF".
4. The power cord type designation is H07RN-F.
Failure or Protection Type
4
Fault Code
Recovery Mode
Recoverable
H0
Recoverable
F1
Recoverable
H4
Irrecoverable
H5
Irrecoverable
H7
Recoverable
H8
Irrecoverable
HF
Recoverable
E1
Recoverable
E2
Recoverable
E4
Recoverable
E5
Recoverable
E6
Recoverable
E7
Recoverable
EH
Eb
Irrecoverable
PL
Recoverable
Recoverable
P1
Recoverable
P2
Recoverable
P3
Recoverable
P4
Recoverable
P5
Recoverable
P8
Recoverable
L0
Recoverable
L1
Recoverable
L2
Recoverable
L4
Recoverable
L5
Recoverable
L7
Recoverable
L8
L9
Recoverable
Recoverable
bH
Recoverable
bL
V.1