6 Settings
6
Settings
6.1
Setting the parameters
Tab.3
Parameter settings
Function
Boiler
Temp differential nominal
Pump modulation
Pump speed min
Pump speed max
Configuration
Relay output QX2
Function output P1
(1) adjust to the system if needed
Tab.4
Parameter settings
Function
Boiler
Pump modulation
Pump speed min
Pump speed max
Configuration
Relay output QX2
Function output P1
(1) adjust to the system if needed
24
Converter PCB module KPM
6.1.1
Boiler pump with speed regulation to a temperature rise
set-point value (e.g. boiler cascade)
Prog. no.
2317
2320
2322
2323
5891
6085
The parameter "Pump speed min" (prog. no. 2322) must be set to the
following values:
30% for Wilo Stratos pumps
10% for Grundfos Magna pumps
The pump function is not guaranteed if values smaller than those specified
are set.
See
The pump manual and in particular the information on the
characteristic pump curve and minimum possible actuation must
be observed.
6.1.2
Boiler pump with speed regulation to the boiler set-point
value for storage tank charging (e.g. buffer vessel or
combi cylinder)
Prog. no.
2320
2322
2323
5891
6085
Important
The parameter "Pump speed min" must be adjusted to the
characteristic pump curve, i.e. prog. no. 2322 must be set such
that the pump is not operated below its minimum characteristic
curve.
See
The pump manual and in particular the information on the
characteristic pump curve and minimum possible actuation must
be observed.
Setting level
Setting value
E
15 °C
(1)
E
3: Temp differential nominal
E
10%
(1)
E
100%
(1)
C
5: Boiler pump Q1
E
1: Boiler pump Q1
Setting level
Setting value
E
2. Boiler setpoint
E
10%
(1)
E
100%
(1)
C
5: Boiler pump Q1
E
1: Boiler pump Q1