6.4 Normativa BDEW 2008
Menú BDEW:
Una vez
ajustes
Exit
1. General
Exit
1. Standard
2. Coupling
3. U
(L-N)
U
(L-L)
4. t
SHORT INT.
5. t
(ON) SHORT INT.
6. t
(ON) NORMAL
7. Remote trip
2. Voltage
Exit
1. U>>
2. t
(OFF)
3. U >
4. t
(OFF)
5. U
(ON) MAX
6. U
(ON) MIN
7. U <
8. t
(OFF)
9. U<<
10. t
(OFF)
3. Frequency
Exit
1. f>>
2. t
(OFF)
3. f>
4. t
(OFF)
5. f
(ON) MAX
6. f
(ON) MIN
7. f<
8. t
(OFF)
9. f<<
10. t
(OFF)
57
Ajuste de
Dos veces
fábrica
4105_2; 4105_1; 4110;
BDEW; 0126; CEI021;
C10/11; G98; G83/2;
G99; G59/2
1 AC; 3N AC; 3 AC
3N AC
50...260 V; 87...450 V
U(L-N) 230 V
off; 40 ms...60 min
off
40 ms...60 min
––
40 ms...60 min
30 s
NC; NO; off
off
off; 100...150 %
120 %
40 ms...60 min
100 ms
off; 100...150 %
108 %
40 ms...60 min
60 s
off; 100...150 %
off
off; 1...100 %
95 %
off; 1...100 %
80 %
40 ms...60 min
2.40 s
off; 1...100 %
45 %
40 ms...60 min
300 ms
off; 50.00...65.00 Hz
off
40 ms...60 min
––
off; 50.00...65.00 Hz
51.50 Hz
40 ms...60 min
100 ms
off; 50.00...65.00 Hz
50.05 Hz
off; 45.00...60.00 Hz
off
off; 45.00...60.00 Hz
47.50 Hz
40 ms...60 min
100 ms
off; 45.00...60.00 Hz
off
40 ms...60 min
––
VMD460-NA_D00001_05_M_XXES/06.2020
Programas básicos