THERMOSTAT PARAMETERS – Only for T–MB and T–MB ± 3°C versions
D
ESCRIPTION
Thermostat NTC probe offset variation
Dead area central point
Dead area setting field
Relay hysteresis
THERMOSTAT PARAMETERS – Only for T–MB ± 3°C version
D
ESCRIPTION
Set variation range with T–MB
PARAMETERS of the T2 probe, CHANGE-OVER
D
ESCRIPTION
Status changeover from ventilation to cooling
Status changeover from ventilation to heating
PARAMETERS of the T3 probe, TME minimum probe
D
ESCRIPTION
Fan ON in heating mode
Fan ON in cooling mode
T3 probe hysteresis
PARAMETERS of the Stratification Cycle
D
ESCRIPTION
Decompensation air probe T1 winter cycle (only for Cassette)
Fan OFF time
RL2 ON time
Post ventilation time
THERMOSTAT PARAMETERS – Only for T–MB–ECM version
D
ESCRIPTION
Speed min. voltage
Speed medium voltage
Speed max. voltage
Speed min. voltage for winter auto fan
Speed max. voltage for winter auto fan
Speed min. voltage for summer auto fan
Speed max. voltage for summer auto fan
Cooling proportional band
Heating proportional band
PARAMETERS of the Pump Timer
D
ESCRIPTION
Pump intervention delay time
OFF time during Summer
ON time during Summer
D
ESCRIPTION
General reset and restore of default values
FEATURES FOR FACTORY
This menu allows modifying the operation
parameters of the thermostat, electronic motor, of the +/- 3 version
and many other parameters (pump cycle, RESET).
With the control set on "OFF", press
the M and Fan buttons simultaneously for 3 seconds.
Select the desired parameter to be modified,
pressing button "+" or "-" and confirm using the "M" button.
Once the parameter is selected, the value will be displayed.
The value can be modified using button "+" or "-".
Press the "M" button once to turn back to the parameter selection;
to exit the menu, press the "M" button for more than 5 seconds.
OTHER FUNCTIONS
34
R
D
ANGE
EFAULT
± 3°C
0°C
18 ÷ 30°C
22°C
1 ÷ 6°C
2°C
0,5 ÷ 2,0°C
0,7°C
R
D
ANGE
EFAULT
± 9°C
± 3°C
R
D
ANGE
EFAULT
15 ÷ 25°C
< 22°C
25 ÷ 35°C
> 32°C
R
D
ANGE
EFAULT
> 30 ÷ 40°C
> 36°C
< 10 ÷ 25°C
< 22°C
2 ÷ 6°C
4°C
R
D
ANGE
EFAULT
0,5 ÷ 2,0°C
1,5°C
5 ÷ 13 min.
10 min.
30 ÷ 120 sec.
40 sec.
5 ÷ 240 sec.
60 sec.
R
D
ANGE
EFAULT
1 ÷ 6
1 V
3 ÷ 8
5 V
6 ÷ 10
10 V
1 ÷ 6
1 V
5 ÷ 10
10 V
1 ÷ 6
1 V
5 ÷ 10
10 V
2,0 ÷ 6,0
3,5°C
2,0 ÷ 6,0
3,5°C
R
D
ANGE
EFAULT
0 ÷ 300 sec.
150 sec.
30 ÷ 90 min.
60 min.
0 ÷ 5 min.
3 min.
O
PERATION
Confirmation with O/I and Fan buttons