STEP FAN CONTROL
Selection of operating speed
Using Fan
key it is possible to select the following
speeds:
AUTO
Automatic fan speed: depending on the set
temperature and the room air temperature
WITH 3-SPEED CONFIGURATIONS AND ON/OFF
VALVE(S) OR W/O VALVE(S):
1 = low speed
2 = medium speed
3 = maximum speed
COOLING
Speed
HEATING
WITH 4-SPEED CONFIGURATIONS AND ON/OFF
VALVE(S) OR W/O VALVE(S):
sm = extra-low speed
1 = low speed
2 = medium speed
3 = maximum speed
Speed
COOLING
HEATING
N.B.: in case of 4-speed configuration and valve, ventila-
tion in heating mode is shifted by 0.5°C to permit
a natural convection phase
WITH 3-SPEED CONFIGURATIONS AND MODULATING
VALVE(S):
1 = low speed
2 = medium speed
3 = maximum speed
Speed
COOLING
Installation and user manual
8
HEATING
WITH 4-SPEED CONFIGURATIONS AND MODULATING
VALVE(S):
sm = extra-low speed
1 = low speed
2 = medium speed
3 = maximum speed
Speed
COOLING
Room
temperature
Speed
HEATING
Room
temperature
 Speed disabled: can be selected only in heating mode and
with 4-speed configuration only. The indoor unit operates
by natural convection only.
Room
temperature
N.B.: In the case of fixed speed, the fan on/off logic will be
Speed
MODULATING FAN
As in the case of step control, the modulating fan control logic
Room
provides for two possible operating modes:
temperature
- automatic operation
- fixed speed operation
The operating mode is selected by pressing the
which switches between the automatic mode (the word AUTO
appears) and the display of the percentage value of the fixed
speed (which flashes in place of the temperature SETPOINT).
While this display mode (the word "FAN" will also flash below
the room temperature value) is active it is possible to change
the speed percentage value using the UP and DOWN buttons
(within any limits set by the manufacturer) and confirm fixed-
speed operation by pressing the
Room
temperature
Extra low speed: can be selected only with
4-speed configuration. It works at extra low
speed only.
Low speed
Medium speed
High speed
equivalent to the automatic logic.
Advanced plus electronic controller
Speed
Room
temperature
Room
temperature
Speed
Room
temperature
button,
button.
FWEC3