WATER CONTROL
Enabling of the heating element is tied to the water temperature.
The related enabling logic is described below.
The enabling signal will not be given if the water sensor is
either not present or disconnected.
DISPLAY
The display shows the following information
 H eating element selected by the user:
symbol
 A ctive heating element:
ECONOMY
The Economy function corrects the setpoint by 2.5°C and
forces the fan to run at the minimum available speed to reduce
unit operation.
 C ooling: setpoint + 2.5°C
 H eating: setpoint - 2.5°C
ACTIVATION
This function can be activated by pressing the key
DISPLAY
The Economy function is shown
on the display by the symbol
MINIMUM TEMPERATURE CONTROL
This logic makes it possible to keep the room temperature from
falling too far when the thermostat is off by forcing the unit into
the heating mode if necessary and for the time required.
If the heating element is present, it will be used only if it was
previously selected as a resource in the heating mode.
SELECTION
When the thermostat is off, you can select the minimum
temperature control by pressing at the same time the keys
.
The same key combination disables this function.
ACTIVATION
If this control is selected, the unit will switch on when the room
temperature falls below 9°C.
When temperature exceeds 10°C the thermostat will resume
the Off status.
N.B.: Any Off command from digital input will disable this
logic.
FWEC3
Advanced plus electronic controller
FC66002765
WATER TEMP.
steadily lit
flashing symbol
.
.
AIR TEMP.
DISPLAY
The display shows the following information
 M inimum temperature control selected: symbol
(displayed only when the thermostat is switched off)
 M inimum temperature control enabled: DEFR indication
DEHUMIDIFICATION
The dehumidification function, enabled only in the cooling
mode, activates operation of the indoor unit in order to achieve
a 10% reduction in the level of humidity present in the room at
the time the function itself was selected.
SELECTION
Dehumidification can be selected/unselected in the Cooling
mode by simultaneously pressing the buttons
In the absence of a water probe (P04=0), or of a remote
humidity probe in cases where the controller is installed directly
on the unit (P08=0), selection will not be enabled. If selected,
the dead band for automatic switching on the air side will be
brought to 5°.
Once selected, the dehumidification logic sets the target
humidity level as the humidity present at the time the function
was selected minus 10%. Where the room humidity is less
than 40% the target level will be set at 30%.
The fan will be forced to run at low speed or, if the temperature
is much higher than the setpoint, at medium speed.
In order to bring the humidity to the set value, the fan (and
valve, if present) will be activated even if the room temperature
has already reached the programmed setpoint (indicated on
the display). Should the room temperature fall too far below
this threshold, the logic will be temporarily inhibited.
.
AIR TEMP.
AIR
TEMP.
Installation and user manual
11