10.8. TECHNICAL MENU
This allows to modify the TECHNICAL
menu parameters listed below
To access the menu, enter the INFO
menu (see procedure described abo-
ve) and then hold the
down for 3 seconds.
Code
SP
Water Set Point [°C]
COMFR
Humidity Set Point
ECO
Humidity Set Point
S3
Ch 3 B3 Probe type
1 = Coil Water
Temperature
(WS)
DIFFH
Differential for Dehumi-
CAL T
Terminal temperature
probe calibration [°C]
CPON
Cycle CP 300" [s]
CPD
Delay CP 30" [s]
DDT
Time between Defrost
DT
Defrost duration [min]
CAL H
Terminal humidity probe
calibration [%rH]
FAND
Delay FAN 10" [s]
SBY D
Dehumidify Standby
22
To exit the TECHNICAL mode, press the
key.
To scroll use the
the parameters, press
+
. keys
values using the
confirm the value using the key
Parameter
Default
15
65
[rH%] Comfort
65
[rH%] Economy
0
10
dification [rH%]
0
24
30
30
[min]
5
0
30
85
and
keys
, To modify
., change the
and
keys and and
..
Range
0..25
Set point for plant water temperature and for dehu-
10.. 1 00
Adjustment set point for Comfort humidity
10.. 1 00
Adjustment set point for Economy humidity
0.. 1
0..30
Differential for dehumidification
-5..+5
Calibration of the temperature probe present on the
24..60
It is expressed in tenths of seconds (240"..600")
10..60
5..50
Time between two defrosts
1.. 1 5
-10..+10
Calibration of the humidity probe present on the
5..60
10.. 1 00
Dehumidification set point in the VACANZA mode
N.B.: before pressing
to modify the
value of a parameter, wait for the current
value of this parameter to be displayed
Notes
midification consent
0 = probe deactivated
terminal
Duration of the defrost
terminal