AERMEC DMP Serie Manual Del Usuario página 25

Deshumidificador para instalaciones de paneles radiantes
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

CHRONO 19 TECHNICAL MENU
NOTE:
THIS PARAGRAPH IS EXCLUSIVELY
FOR THE TECHNICAL AFTER-SALES
SERVICE, OR WHOEVER IN AUTHO-
RITY.
This allows to modify the TECHNICAL
menu parameters listed below.
To access the menu, enter the INFO
CODE
CODE
Set AC
Set Hc
Set HE
TYP 3
Dif H
CAL A
CP ON
CP DEL
Auto
DEFMi
DEFMa
CAL H
Delay
menu and hold the
down for 3 seconds.
To exit the TECHNICAL mode, press the
key.
Scroll the menu using the
keys. To modify the parameters use the
and
keys.
PARAMETER
Water Set Point [°C]
Humidity Set Point [rH%] Comfort
Humidity Set Point [rH%] Economy
Ch 3 B3 Probe type
Differential for Dehumidification [rH%]
Terminal temperature probe calibration
[°C]
Cycle CP 300" [s]
Delay CP 30" [s]
Automatic Restart
Time between two defrosts (min)
Defrost duration [min]
Terminal humidity probe calibration [%rH]
Delay FAN 10" [s]
+
keys
and
DEFAULT
RANGE
NOTES
Set point for plant water tempe-
15
0..25
rature and for dehumidification
consent
Adjustment set point for Com-
65
10.. 1 00
fort humidity
Adjustment set point for Eco-
65
10.. 1 00
nomy humidity
0 = probe deactivated
0
0.. 1
1 = Coil Water Temperature
(WS)
10
0..30
Differential for dehumidification
Calibration of the temperature
0
-5..+5
probe present on the terminal
It is expressed in tenths of
24
24..60
seconds (240"..600")
30
10..60
0
0
0.. 1
1
30
5..50
Time between two defrosts
5
1.. 1 5
Duration of the defrost
Calibration of the humidity pro-
0
-10..+10
be present on the terminal
30
5..60
no restart
automatic restart
25

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Dmp20

Tabla de contenido